SUBFUNCTION
5 Circuit B Analog Values (cont)
6 Circuit B Discrete Inputs/Outputs
7 Unit Analog Parameters
See Legend on page 25.
Table 13 — Status Function and Subfunction Directory (cont)
KEYPAD ENTRY
DISPLAY
B1 Motor Temperature
xxx.x dF
B2 Motor Temperature
xxx.x dF
SAT Condensing Temp
xxx.x dF
Saturated Suction Temp
xxx.x dF
EXV Percent Open
xxx.x%
Motormaster Speed
xxx.x%
Water Valve Position
xxx.x%
Cooler Level Indicator
x.xx
CPM B1 Feedback
x.x Volts
CPM B2 Feedback
x.x Volts
Circuit B Econ Pressure
xxx.x PSI
CIR. B DISCRETE OUTPUTS
Compressor B1
Off/On
Compressor B2
Off/On
Loader B1
Off/On
Loader B2
Off/On
Minimum Load Valve B
Off/On
Circuit B Oil Heater
Off/On
B1 Mtr Cooling Solenoid
Off/On
B2 Mtr Cooling Solenoid
Off/On
Circuit B Oil Pump
Off/On
Oil Solenoid B1
Off/On
Oil Solenoid B2
Off/On
CIR. B DISCRETE INPUTS
Circuit B Oil Switch
Open/Close
Compressor B1 Feedback
Off/On
Compressor B2 Feedback
Off/On
UNITS ANALOG PARAMETERS
Cooling Entering Fluid
xx.x dF
Cooling Leaving Fluid
xx.x dF
Condenser Entering Fluid
xx.x dF
Condenser Leaving Fluid
xx.x dF
Reclaim Entering Fluid
xx.x dF
Reclaim Leaving Fluid
xx.x dF
5 Volt Supply
x.x Volts
22
COMMENT
See Table 5.