Carrier Ecologic Series 3 Controls, Start-Up, Operation, Service, And Troubleshooting page 31

Air-cooled and fluid cooled chillers. 50/60 hz
Table of Contents

Advertisement

SUBFUNCTION
1 Set Point Table
2 Units
3 Address
4 Time
5 CCN Disable
LEGEND
CCN — Carrier Comfort Network
dF
— Degrees Fahrenheit
LCW — Leaving Chilled Water
NOTE: If metric option is selected under
expressed in degrees Celsius and pressures are expressed in kPa.
Table 20 — Set Point Function and Subfunction Directory
KEYPAD ENTRY
ENTER
ENTER
ENTER
ENTER
ENTER
, temperatures are
DISPLAY
COOLING
Cool Setpoint 1
x.xx dF
Cool Setpoint 2
xx.x dF
Cooling Ramp Loading
xx.x dF
HEATING
Heat Setpoint 1
xx.x dF
Heat Setpoint 2
xx.x dF
Heating Ramp Loading
xx.x dF
HEAD PRESSURE
Head Pressure Setpoint A
xxx.x dF
Head Pressure Setpoint B
xxx.x dF
DEMAND LIMIT
Demand Switch 1 Setpoint
xxx.x%
Demand Switch 2 Setpoint
xxx.x%
LCW Delta Alarm Limit
xxx.x dF
Minutes Off Time
xxx min
Motor Temp Set Point
xxx.x dF
US IMPERIAL/METRIC
0
TARGET ADDRESS
x
TARGET BUS NUMBER
x
Day of Week
Monday
Day of Week
Wednsday
TIME (HOUR/MIN)
00:00
TIME (HOUR/MIN)
10:30
DAY OF MONTH
xx
DAY OF MONTH
20
MONTH OF YEAR
xx
MONTH OF YEAR
05
YEAR OF CENTURY
xx
YEAR OF CENTURY
96
Disable CCN Control
x
31
COMMENT
Default: 44.0
Default: 44.0
Default: 0.5
NOT SUPPORTED
NOT SUPPORTED
Default: 98.0
NOT SUPPORTED
Default: 98.0
NOT SUPPORTED
Default: 0.5
Default: 113.0 (GX)
100.0 (HXA) 85.0 (HXC)
Default: 113.0 (GX)
100.0 (HXA) 85.0 (HXC)
Default: 80.0%
Default: 50.0%
Default: 50.0 dF
Default: 0 min
Default: 200.0 dF
0 = English (Default)
1 = Metric
Default: 1
Default: 0
Mon=1, Tues=2, etc.
Day of week set
Enter military format
Time of day set
Day of month set
Month of year set
Year of century set
0=no, 1=yes
Default: 0