Table 22 — Service Function and Subfunction Directory (cont)
SUBFUNCTION
4 Reset Configuration Table (cont)
5 Factory Configuration Codes
6 NOT USED
7 Transducer Calibration
See Legend on page 36.
KEYPAD ENTRY
Demand Limit Select
x
Loadshed Group Number
x
Loadshed Demand Delta
xxx%
Maximum Loadshed Time
xx min
WATER VALVE PID
Proportional PID Gain
x.x
Integral PID Gain
x.x
Derivative PID Gain
x.x
AIR MOTOR MASTER
PID
Proportional PID Gain
x.x
Integral PID Gain
x.x
Derivative PID Gain
x.x
FACTORY CODES
Configuration Code 1
xxxxxxxx
Configuration Code 2
xxxxxxxx
Configuration Code 3
xxxxxxxx
SERVICE CODES
Configuration Code 4
xxxxxxxx
Configuration Code 5
xxxxxxxx
CALIBRATION OFFSET
CIRCUIT A PRESSURE
Discharge Pressure
xxx.x PSI
Suction Pressure
xxx.x PSI
A1 Oil Pressure
xxx.x PSI
A2 Oil Pressure
xxx.x PSI
Economizer Pressure
xxx.x PSI
CALIBRATION OFFSET
CIRCUIT B PRESSURE
Discharge Pressure
xxx.x PSI
Suction Pressure
xxx.x PSI
B1 Oil Pressure
xxx.x PSI
B2 Oil Pressure
xxx.x PSI
Economizer Pressure
xxx.x PSI
DISPLAY
0 = None (Default), 1 = Two-step switch,
2 = 4-20 mA, 3 = CCN Loadshed
0-99, Default: 0
0-60%, Default: 0
0-120 min, Default: 60 min
Default = 1.0
Adjustable from -20.0 to 20.0
Default = 0.1
Adjustable from -20.0 to 20.0
Default = 0.0
Adjustable from -20.0 to 20.0
Default = 1.0
Adjustable from -20.0 to 20.0
Default = 0.1
Adjustable from -20.0 to 20.0
Default = 0.0
Adjustable from -20.0 to 20.0
Factory set. See Table 25.
Factory set. See Table 25.
Factory set. See Table 25.
Factory set. See Table 25.
Factory set. See Table 25.
See Pressure Transducer Calibration, page 61.