Table 42B — Thermistor Temperatures (°C) vs Resistance/Voltage Drop
(NOTE: These values do NOT Apply to the Motor Temperature Thermistors)
VOLTAGE
TEMP
DROP
(C)
(V)
–40
4.896
–39
4.889
–38
4.882
–37
4.874
–36
4.866
–35
4.857
–34
4.848
–33
4.838
–32
4.828
–31
4.817
–30
4.806
–29
4.794
–28
4.782
–27
4.769
–26
4.755
–25
4.740
–24
4.725
–23
4.710
–22
4.693
–21
4.676
–20
4.657
–19
4.639
–18
4.619
–17
4.598
–16
4.577
–15
4.554
–14
4.531
–13
4.507
–12
4.482
–11
4.456
–10
4.428
–9
4.400
–8
4.371
–7
4.341
–6
4.310
–5
4.278
–4
4.245
–3
4.211
–2
4.176
–1
4.140
0
4.103
1
4.065
2
4.026
3
3.986
4
3.945
5
3.903
6
3.860
7
3.816
8
3.771
9
3.726
THERMISTOR JACKETED CABLE
PLUG END
PACKING NUT
FERRULE
RESISTANCE
TEMP
(Ohms)
(C)
168,230
10
157,440
11
147,410
12
138,090
13
129,410
14
121,330
15
113,810
16
106,880
17
100,260
18
94,165
19
88,480
20
83,170
21
78,125
22
73,580
23
69,250
24
65,205
25
61,420
26
57,875
27
54,555
28
51,450
29
48,536
30
45,807
31
43,247
32
40,845
33
38,592
34
38,476
35
34,489
36
32,621
37
30,866
38
29,216
39
27,633
40
26,202
41
24,827
42
23,532
43
22,313
44
21,163
45
20,079
46
19,058
47
18,094
48
17,184
49
16,325
50
15,515
51
14,749
52
14,026
53
13,342
54
12,696
55
12,085
56
11,506
57
10,959
58
10,441
59
SENSOR TUBE
BEND SLIGHTLY BEFORE WELL INSERTION
4 in.
Fig. 22 — Thermistor Replacement (T1, T2, T5, or T6)
Fig. 23 — Thermistor (Liquid Level Sensor) Replacement
VOLTAGE
RESISTANCE
DROP
(Ohms)
(V)
3.680
9,949
3.633
9,485
3.585
9,044
3.537
8,627
3.487
8,231
3.438
7,855
3.387
7,499
3.337
7,161
3.285
6,840
3.234
6,536
3.181
6,246
3.129
5,971
3.076
5,710
3.023
5,461
2.970
5,225
2.917
5,000
2.864
4,786
2.810
4,583
2.757
4,389
2.704
4,204
2.651
4,028
2.598
3,861
2.545
3,701
2.493
3,549
2.441
3,404
2.389
3,266
2.337
3,134
2.286
3,008
2.236
2,888
2.186
2,773
2.137
2,663
2.087
2,559
2.039
2,459
1.991
2,363
1.944
2,272
1.898
2,184
1.852
2,101
1.807
2,021
1.763
1,944
1.719
1,871
1.677
1,801
1.635
1,734
1.594
1,670
1.553
1,609
1.513
1,550
1.474
1,493
1.436
1,439
1.399
1,387
1.363
1,337
1.327
1,290
3/16 in.
MEASURE TO TOP
OF WELD COUPLING
FOR PROPER
INSERTION
(SEE TABLE 44)
COOLER
63
VOLTAGE
TEMP
RESISTANCE
DROP
(C)
(Ohms)
(V)
60
1.291
1,244
61
1.258
1,200
62
1.225
1,158
63
1.192
1,118
64
1.160
1,079
65
1.129
1,041
66
1.099
1,006
67
1.069
68
1.040
69
1.012
70
0.984
71
0.949
72
0.920
73
0.892
74
0.865
75
0.838
76
0.813
77
0.789
78
0.765
79
0.743
80
0.722
81
0.702
82
0.683
83
0.665
84
0.648
85
0.632
86
0.617
87
0.603
88
0.590
89
0.577
90
0.566
91
0.555
92
0.545
93
0.535
94
0.525
95
0.515
96
0.506
97
0.496
98
0.486
99
0.476
100
0.466
101
0.454
102
0.442
103
0.429
104
0.416
105
0.401
106
0.386
107
0.370
THERMISTOR WELL
X
971
938
906
876
836
805
775
747
719
693
669
645
623
602
583
564
547
531
516
502
489
477
466
456
446
436
427
419
410
402
393
385
376
367
357
346
335
324
312
299
285

Hide quick links: