PERFORM TEST FUNCTION (INDICATE POSITIVE RESULT):
ONCE POWER IS SUPPLIED TO THE UNIT, CHECK THE DISPLAY FOR ANY ALARMS, SUCH AS PHASE REVERSAL.
FOLLOW THE TEST FUNCTION INSTRUCTIONS IN THE CONTROLS AND TROUBLESHOOTING LITERATURE. BE
SURE TO CHECK FOR PROPER FAN ROTATION WITH THE FAN TEST SECTIONS. BE SURE ALL SERVICE VALVES
ARE OPEN BEFORE BEGINNING THE COMPRESSOR TEST SECTION. ITEMS MARKED WITH "†" CAN BE TESTED
ONLY IF THE UNIT IS CONFIGURED FOR THIS OPTION. DO NOT RUN OIL PUMPS FOR MORE THAN 20 SECONDS.
LOADER A1
LOADER A2
MINIMUM LOAD VALVE A†
CIRCUIT A OIL HEATER
A1 MOTOR COOLING SOLENOID
A2 MOTOR COOLING SOLENOID†
CIRCUIT A OIL PUMP
OIL SOLENOID A1
OIL SOLENOID A2†
CIRCUIT A EXV
CIRCUIT B EXV
CIRCUIT A WATER VALVE†
CIRCUIT A% FAN SPEED (GX)†
CIRCUIT B% FAN SPEED (GX)†
COMPRESSOR A1
COMPRESSOR A2†
COMPRESSOR B1
COMPRESSOR B2†
CHECK FOR COMMUNICATING MODULES (BLINKING RED AND GREED LEDs)
CORRECT FLUID SET POINTS ARE ENTERED
COOL SET POINT 1 _____________
COOL SET POINT 2 _____________
CORRECT DATE, TIME, AND OPERATING SCHEDULE(S) ARE SET
LOADER B1
LOADER B2
MINIMUM LOAD VALVE B†
CIRCUIT B OIL HEATER
B1 MOTOR COOLING SOLENOID
B2 MOTOR COOLING SOLENOID†
CIRCUIT B OIL PUMP
OIL SOLENOID B1
OIL SOLENOID B2†
FAN 1 (30GX)†
FAN 2 (30GX)†
FAN 3 (30GX)†
FAN 4 (30GX)†
FAN 5 (30GX)†
FAN 6 (30GX)†
COOLER PUMP†
CONDENSER PUMP†
COOLER HEATER†
ALARM RELAY†