Carrier Ecologic Series 3 Controls, Start-Up, Operation, Service, And Troubleshooting page 28

Air-cooled and fluid cooled chillers. 50/60 hz
Table of Contents

Advertisement

SUBFUNCTION
1 Circuit A Discrete Outputs
2 Circuit B Discrete Outputs
3 Unit Discrete Outputs
Table 17 — Test Function and Subfunction Directory
KEYPAD ENTRY
Circuit A Discrete Output Loader A1
Relay is OFF
Loader A1
ENTER
Relay is ON
Loader A2
Minimum Load Valve A
Circuit A Oil Heater
A1 Mtr. Cooling Solenoid
A2 Mtr. Cooling Solenoid
Circuit A Oil Pump
Oil Solenoid A1
Oil Solenoid A2
Circuit B Discrete Output Loader B1
Relay is OFF
Loader B1
ENTER
Relay is ON
Loader B2
Minimum Load Valve B
Circuit B Oil Heater
B1 Mtr. Cooling Solenoid
B2 Mtr. Cooling Solenoid
Circuit B Oil Pump
Oil Solenoid B1
Oil Solenoid B2
Unit Discrete Output Fan 1
Relay is OFF
Fan 1
ENTER
Relay is ON
Fan 2
Fan 3
Fan 4
Fan 5
Fan 6
Cooler Pump
Condenser Pump
Cooler Heater
Alarm
Remote Alarm 1
DISPLAY
Similarly, use
the down arrow key or
NOTE: Output will display Relay is ABSENT when not
configured
Similarly, use
Press the down arrow key or
output off.
NOTE: Output will display Relay is ABSENT when not
configured
Similarly, use
Press the down arrow key or
output off.
Energizes Circuit A fans for 30HXA units.
Energizes Circuit B fans for 30HXA units.
Currently not supported.
28
COMMENT
to test remaining outputs. Press
ENTER
to turn an output off.
ENTER
to test remaining outputs.
ENTER
to turn an
ENTER
to test remaining outputs.
ENTER
to turn an
ENTER