Download Print this page
Carrier 30GXN Installation Instructions Manual
Carrier 30GXN Installation Instructions Manual

Carrier 30GXN Installation Instructions Manual

Minimum load control accessory 50/60 hz

Advertisement

Quick Links

CONTENTS
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . 1
INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-8
Step 1 — Examine Package Contents . . . . . . . . . . . . 1
Step 2 — Install Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
• REMOVE MINIMUM LOAD PORT PLUGS
AND INSTALL FITTINGS
• INSTALL PIPING
• INSTALL BALL AND SOLENOID VALVES
• CONNECT PIPING
• 30GXN,R UNITS ONLY
Step 3 — Dehydrate and Recharge Circuit. . . . . . . . 3
Step 4 — Install Control Wiring. . . . . . . . . . . . . . . . . . . 3
• 30HX UNITS
• 30GXN,R UNITS
• ALL UNITS
Step 5 — Configure Unit for Minimum
Load Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Step 6 —Test Minimum Load Relay
Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Step 7 — Adjust Setting of Minimum
Load Ball Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
SAFETY CONSIDERATIONS
Installing, starting up, and servicing air-conditioning equip-
ment can be hazardous due to system pressures, electrical com-
ponents, and equipment location.
Only trained, qualified installers and service technicians
should install, start up, and service this equipment.
When working on air-conditioning equipment, observe pre-
cautions in the literature and on tags, stickers, and labels
attached to the equipment.
Follow all safety codes. Wear safety glasses and work
gloves. Use care in handling equipment.
Be sure power to equipment is shut off before performing
maintenance or service.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
PC 903
Catalog No. 533-00009
Book 2
Tab
5c

Installation Instructions

Part No. 30GX-900---048,
(60 Hz — 115-v Control)
Part No. 30GX-900---049
(50 or 60 Hz — 230-v Control)
Page
Printed in U.S.A.
Minimum Load Control Accessory
IMPORTANT: When removing refrigerant, use an
approved refrigerant recovery device. Do not vent refrig-
erant into the atmosphere.
INTRODUCTION
The minimum load control accessory allows 30HX and
30GXN,R chillers to have their capacities decreased below the
standard fully unloaded condition. The accessory provides
more precise control of leaving fluid temperature during light
load conditions.
The 30GXN,R and 30HX chillers have a dual-circuit
design. Each minimum load control accessory package con-
tains the items required for both circuits. Because of an auto-
matic lead/lag feature on the chillers, the accessory should be
installed on both circuits.
INSTALLATION
Step 1 — Examine Package Contents —
age includes solenoid valves, ball valves, O-ring seal fittings,
and instructions. Examine each item. If any part is damaged or
missing, file a claim immediately with the shipper and notify
your Carrier representative. See Table 1 for accessory package
contents and field-supplied material.
Table 1 — Accessory Package Contents
and Field-Supplied Material
ACCESSORY PACKAGE
COMPONENTS
Solenoid Valve
Ball Valve
O-Ring Seal Fitting
Tube Assembly
Tube Assembly (Condenser
Oil Separator)
FIELD SUPPLIED MATERIAL — REQUIRED PARTS
(Ordered Separately)
5
/
-in. OD Copper Tubing, Wiring, Conduit,
8
Thread Sealant, Electrical Supplies
Form 30GX,HX-14SI
Pg 1
30GXN,R080-528
30HX076-271
50/60 Hz
ACCESSORY PART NUMBER
30GX-900---048
30GX-900---049
(2) EF23JX212
(2) EF23JX231
(2) EP71BA201
(2) EP71BA201
(4) 30GX503492
(4) 30GX503492
(2) 30GX503487
(2) 30GX503457
(2) 30HX402343
(2) 30HX402343
Field Supplied
102
7-00
Replaces: 30GX,HX-7SI
Pack-

Advertisement

loading

Summary of Contents for Carrier 30GXN

  • Page 1: Installation Instructions

    Do not vent refrig- erant into the atmosphere. The minimum load control accessory allows 30HX and 30GXN,R chillers to have their capacities decreased below the standard fully unloaded condition. The accessory provides more precise control of leaving fluid temperature during light load conditions.
  • Page 2: Step 2 - Install Piping

    Fittings should be installed with similar sealant on threads. 30GXN,R — Cut plug end off of minimum load port braze nipple on discharge line, located between oil separator and con- denser. Remove plug from minimum load port on cooler shell.
  • Page 3 Fig. 2 — Installing Fittings and Valves, 30HX (Typical) 30GXN,R UNITS ONLY — Using good brazing practice, braze the -in. minimum load tubing to the copper nipple on the discharge line (minimum load port) between the condenser coil and oil separator. See Fig. 1, 3A and 3B.
  • Page 4 CONTROL PORTS CIRCUIT A (080-138) CIRCUIT B (150, 160) CIRCUIT B (080-138) CIRCUIT A (150, 160) → Fig. 3A — Typical Piping and Valve Installation 30GXN,R080-178 and Associated Modular Sizes (080-150, 160 Shown) O-RING SEAL FITTING SOLENOID DETAIL C VALVE...
  • Page 5 — Equipment — Electronic Expansion Valve — Fuse Block — Fan Relay GFI-CO — Ground Fault Interrupter Convenience Outlet *And associated modular sizes. → 30GXN,R080-178* MLC-A CONDUIT 30HX076-186 LEGEND — Ground — Loader Relay — Minimum Load Control — Oil Pump Contactor —...
  • Page 6 MLC-B CONDUIT *And associated modular sizes. → Fig. 4 — Typical Minimum Load Control Wiring (cont) MLC-A CONDUIT 30HX206-271 30GXN,R204-350*...
  • Page 7 Fig. 4 — Typical Minimum Load Control Wiring (cont) ROUTE CONDUITS THROUGH TRAY AND ATTACH TO BOTTOM OF SHELF ON TB-4 SIDE OF CONTROL BOX Fig. 5 — Routing Field-Supplied Wiring and Conduit (30GXN,R Shown)
  • Page 8: Enter Password

    NOTE: Operation of the chiller in Manual Control mode is described in the Controls, Start-Up, Operation, and Trouble- shooting Guide that is included with the 30GXN,GXR,HX ComfortLink™ chillers. 3. Record the cooler ∆T (the difference between cooler en- tering fluid temperature and cooler leaving fluid tempera- ture) at this fully unloaded condition.

This manual is also suitable for:

R080-52830gxr30hx