Wiring
6.2.1

Connecting the power supply

Screw-type terminal block
The 24 VDC load power supply required is connected at the screw-type terminal
block.
Properties of the load power supply
Danger
!
The 24 VDC should be configured as function low-voltage with safe isolation.
Note
The connection cable between the voltage source and the load current supply con-
nector L+ and the associated reference potential M should not exceed a maximum
length of 10 m.
Table 6-1
Voltage range – mean value
Ripple
Transient overvoltage
Rated power consumption
Starting current
Pin connections
The table below shows the pin connections on the screw-type terminal block.
Table 6-2
M
L+
M
If you wish to ground the reference potential, you must not remove the jumper be-
tween terminals M and the functional ground on the C230-2.
6-86
Electrical parameters of load power supply
Parameters
Assignment of the screw-type terminal block
Terminal
Min
Max
Unit
20.4
28.8
V
3.6
Vpp
35
V
2.2
A
8
A
Functional ground
Ground
24 VDC
Ground
E Siemens AG, 2003 All rights reserved
SIMOTION C230-2, 04.2003 Edition
Conditions
500 ms continuous
50 s recovery time
See Section 3.4
"Connection values"