Device Data
Connecting cable to the encoder
The maximum cable length depends on the specification for the encoder supply
and the baud rate. If you use pre-assembled SIEMENS connecting cables (see
Catalogs NC Z/NC 60/ST 70), problem-free operation can be guaranteed only if
the following values are not exceeded:
Table 3-9
Supply voltage
5 VDC
5 VDC
24 VDC
24 VDC
Table 3-10
Incremental encoder
Absolute encoder (SSI)
3-40
Maximum cable lengths, depending on the encoder power supply
Encoder supply
voltage range
4.75 V...5.25 V
4.75 V...5.25 V
20.4 V...28.8 V
11 V...30 V
Maximum cable lengths, depending on the baud rate
Encoder type
Power con-
Max. cable length
sumption
< 300 mA
< 210 mA
< 300 mA
< 300 mA
Frequency
Max. cable length
1 MHz
500 kHz
1.5 Mbits/s
187.5 Kbyte/s
E Siemens AG, 2003 All rights reserved
SIMOTION C230-2, 04.2003 Edition
25 m
35 m
100 m
250 m
10 m
35 m
10 m
250 m