Wiring

6.7 Connecting system power supply and load current supply

Connection of wires: multi-wire (stranded), without end sleeve, unprocessed
To connect a wire without end sleeve, follow these steps:
1. Strip 8 to 11 mm of the wires.
2. Using a screwdriver, press the spring release and insert the wire into the push-in terminal
as far as it will go.
3. Pull the screwdriver out of the spring release.
4. Push the wired connector into the socket of the CPU/interface module.
Loosening a wire
Push with the screwdriver as far as it will go into the spring release. Remove the wire.
Uninstalling the connection plug
To uninstall the connection plug, you need a screwdriver. With the screwdriver, pry the
connection plug out of the CPU/interface module.
6.7
Connecting system power supply and load current supply
Introduction
In the delivery condition of the system power supplies/load current supplies, power
connectors are inserted. The modules and the associated power connectors are coded. The
coding is effected by means of two coding elements - one coding element is located in the
module, and the other in the power connector. The system power supplies/load current
supplies use identical power connectors for the voltage connection.
The coding element prevents the insertion of a power connector into a different type of
system power supply/load current supply.
Tools required
3 to 3.5 mm screwdriver