C: Tuning; C1: Accel & Decel Time; C2: S-Curve Characteristics - YASKAWA CIPR-GA50C series Technical Manual

Ac micro drives for industrial applications. 200 v class, three-phase input: 0.1 to 22 kw. 200 v class, single-phase input: 0.1 to 4.0 kw. 400 v class, three-phase input: 0.37 to 30 kw.
Table of Contents

Advertisement

11.6 C: Tuning

11.6

C: Tuning

C1: Accel & Decel Time
No.
Name
(Hex.)
C1-01
Acceleration Time 1
(0200)
RUN
C1-02
Deceleration Time 1
(0201)
RUN
C1-03
Acceleration Time 2
(0202)
RUN
C1-04
Deceleration Time 2
(0203)
RUN
C1-05
Acceleration Time 3
(0204)
RUN
C1-06
Deceleration Time 3
(0205)
RUN
C1-07
Acceleration Time 4
(0206)
RUN
C1-08
Deceleration Time 4
(0207)
RUN
C1-09
Fast Stop Time
(0208)
RUN
C1-10
Accel/Decel Time
Setting Units
(0209)
C1-11
Accel/Decel Time
Switching Frequency
(020A)
C1-14
Accel/Decel Rate
Frequency
(0264)
RUN

C2: S-Curve Characteristics

No.
Name
(Hex.)
C2-01
S-Curve Time @ Start of
Accel
(020B)
C2-02
S-Curve Time @ End of
Accel
(020C)
C2-03
S-Curve Time @ Start of
Decel
(020D)
C2-04
S-Curve Time @ End of
Decel
(020E)
348
Description
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the length of time to accelerate from zero to maximum output frequency.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the length of time to decelerate from maximum output frequency to zero.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the length of time to accelerate from zero to maximum output frequency.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the length of time to decelerate from maximum output frequency to zero.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the length of time to accelerate from zero to maximum output frequency.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the length of time to decelerate from maximum output frequency to zero.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the length of time to accelerate from zero to maximum output frequency.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the length of time to decelerate from maximum output frequency to zero.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the length of time that the drive will decelerate to zero for a Fast Stop.
Note:
• Decelerating too quickly can cause an ov [Overvoltage] fault that shuts off the
drive while the motor to coasts to a stop. Set a Fast Stop time in C1-09 that
prevents motor coasting and makes sure that the motor stops quickly and safely.
• When L2-29 = 0 [Kinetic Energy Backup Method = Single Drive KEB Ride-Thru
1] and you do KEB Auto-Tuning, the drive will automatically set C1-09. If you
must not change the Fast Stop time, do not do KEB Tuning.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the setting units for C1-01 to C1-08 [Accel/Decel Times 1 to 4], C1-09 [Fast Stop
Time], L2-06 [Kinetic Energy Backup Decel Time], and L2-07 [Kinetic Energy Backup
Accel Time].
0 : 0.01 s (0.00 to 600.00 s)
1 : 0.1 s (0.0 to 6000.0 s)
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the frequency at which the drive will automatically change acceleration and
deceleration times.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the base frequency used to calculate acceleration and deceleration rates.
Description
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the S-curve acceleration time at start.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the S-curve acceleration time at completion.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the S-curve deceleration time at start.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the S-curve deceleration time at completion.
Default
(Range)
10.0 s
(0.0 - 6000.0 s)
10.0 s
(0.0 - 6000.0 s)
10.0 s
(0.0 - 6000.0 s)
10.0 s
(0.0 - 6000.0 s)
10.0 s
(0.0 - 6000.0 s)
10.0 s
(0.0 - 6000.0 s)
10.0 s
(0.0 - 6000.0 s)
10.0 s
(0.0 - 6000.0 s)
10.0 s
(0.0 - 6000.0 s)
1
(0, 1)
Determined by A1-02
(0.0 - 590.0 Hz)
0.0 Hz
(0.0 - 590.0 Hz)
Default
(Range)
Determined by A1-02
(0.00 - 10.00 s)
0.20 s
(0.00 - 10.00 s)
0.20 s
(0.00 - 10.00 s)
0.00 s
(0.00 - 10.00 s)
YASKAWA SIEPC71061753A GA500 Technical Manual
Ref.
521
522
522
522
522
522
522
523
523
523
523
524
Ref.
526
526
526
526

Advertisement

Table of Contents
loading

This manual is also suitable for: