External Interlock - YASKAWA CIPR-GA50C series Technical Manual

Ac micro drives for industrial applications. 200 v class, three-phase input: 0.1 to 22 kw. 200 v class, single-phase input: 0.1 to 4.0 kw. 400 v class, three-phase input: 0.37 to 30 kw.
Table of Contents

Advertisement

3.8

External Interlock

For applications that will have unwanted effects on the system if the drive stops, make an interlock between
MFDO terminals set to H2-xx = E [MFDO Function Selection = Fault] and H2-xx = 6 [Drive Ready].
Drive Ready
When the drive is operating or is prepared to accept a Run command, the MFDO terminal to which Drive Ready
[H2-xx = 6] is set will enter the ON status.
In these conditions, Drive Ready is OFF and the drive ignores Run commands:
• The drive is de-energized
• During a fault
• There is problem with the control power supply
• There is a parameter setting error that will not let the drive run, although a Run command is entered
• An overvoltage or undervoltage fault occurs when the Run command is entered
• The drive is in Programming Mode.
Interlock Circuit Example
Refer to
Figure 3.49
for an example of how two drives that run one application use the Drive Ready and Fault
output signals to interlock with the controller.
Terminal
MA, MB, MC
P1-C1
YASKAWA SIEPC71061753A GA500 Technical Manual
Output Signal
Fault
Drive Ready
Figure 3.49 Interlock Circuit Example

3.8 External Interlock

Parameter Settings for Output Signal
H2-01 = E
H2-02 = 6
3
93

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ga500 series

Table of Contents