F: Options; F1: Fault Detection In Pg Speed Control - YASKAWA CIPR-GA50C series Technical Manual

Ac micro drives for industrial applications. 200 v class, three-phase input: 0.1 to 22 kw. 200 v class, single-phase input: 0.1 to 4.0 kw. 400 v class, three-phase input: 0.37 to 30 kw.
Table of Contents

Advertisement

11.9

F: Options

F1: Fault Detection in PG Speed Control

No.
Name
(Hex.)
F1-02
Encoder Signal Loss
Detect Sel
(0381)
F1-03
Overspeed Detection
Selection
(0382)
F1-04
Speed Deviation
Detection Select
(0383)
F1-08
Overspeed Detection
Level
(0387)
F1-09
Overspeed Detection
Delay Time
(0388)
F1-10
Speed Deviation
Detection Level
(0389)
YASKAWA SIEPC71061753A GA500 Technical Manual
Description
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the method to stop the motor or let the motor continue operating when the drive
detects PGo [Encoder (PG) Feedback Loss].
0 : Ramp to Stop
1 : Coast to Stop
2 : Fast Stop (Use C1-09)
3 : Alarm Only
4 : No Alarm Display
Note:
When A1-02 = 0 [Control Method Selection = V/f], set H6-01 = 3 [Terminal RP
Pulse Train Function = Speed Feedback (V/F Control)] to enable this parameter.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the method to stop the motor or let the motor continue to operate when the drive
detects oS [Overspeed].
0 : Ramp to Stop
1 : Coast to Stop
2 : Fast Stop (Use C1-09)
3 : Alarm Only
Note:
When A1-02 = 0 [Control Method Selection = V/f], set H6-01 = 3 [Terminal RP
Pulse Train Function = Speed Feedback (V/F Control)] to enable this parameter.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the method to stop the motor or let the motor continue to operate when the drive
detects dEv [Speed Deviation].
0 : Ramp to Stop
1 : Coast to Stop
2 : Fast Stop (Use C1-09)
3 : Alarm Only
Note:
When A1-02 = 0 [Control Method Selection = V/f], set H6-01 = 3 [Terminal RP
Pulse Train Function = Speed Feedback (V/F Control)] to enable this parameter.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the detection level of oS [Overspeed] as a percentage when the maximum output
frequency is 100%.
Note:
• Parameter A1-02 [Control Method Selection] selects which parameter is the
maximum output frequency.
–A1-02 ≠ 8 [EZOLV]: E1-04 [Maximum Output Frequency]
–A1-02 = 8: E9-02 [Motor Max Revolutions]
• When A1-02 = 0 [Control Method Selection = V/f], set H6-01 = 3 [Terminal RP
Pulse Train Function = Speed Feedback (V/F Control)] to enable this parameter.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the length of time that the speed feedback must be more than the F1-08 level to
cause oS [Overspeed].
Note:
When A1-02 = 0 [Control Method Selection = V/f], set H6-01 = 3 [Terminal RP
Pulse Train Function = Speed Feedback (V/F Control)] to enable this parameter.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the detection level of dEv [Speed Deviation] as a percentage when the maximum
output frequency is 100%.
Note:
• Parameter A1-02 [Control Method Selection] selects which parameter is the
maximum output frequency.
–A1-02 ≠ 8 [EZOLV]: E1-04 [Maximum Output Frequency]
–A1-02 = 8: E9-02 [Maximum Speed]
• When A1-02 = 0 [Control Method Selection = V/f], set H6-01 = 3 [Terminal RP
Pulse Train Function = Speed Feedback (V/F Control)] to enable this parameter.

11.9 F: Options

Default
Ref.
(Range)
1
576
(0 - 4)
1
576
(0 - 3)
3
577
(0 - 3)
115%
577
(0 - 120%)
Determined by A1-02
578
(0.0 - 2.0 s)
10%
578
(0 - 50%)
361
11