6.2.2
Commissioning and startup of ET 200S on PROFIBUS DP
6.2.2.1
Setting the PROFIBUS Address
Introduction
The PROFIBUS address is used to specify the address of the ET 200S distributed I/O
system on PROFIBUS DP.
● The PROFIBUS DP address for the ET 200S is set on the interface module or COMPACT
● Valid PROFIBUS DP addresses are 1 to 125.
● Each address can be assigned only once on PROFIBUS DP.
Requirements
Address setting is not yet assigned on PROFIBUS DP.
Required tools
3-mm screwdriver
ET 200S
Operating Instructions, 08/2008, A5E00515771-06
module by means of DIP switches. The DIP switches are to be found on the front of the
interface module, protected by a sliding window.
6.2 Commissioning on PROFIBUS DP
Commissioning
111