Software Required For Commissioning; Prerequisite For Commissioning The Et 200Eco; Steps For Commissioning The Dp Slave; Et 200Eco Commissioning And Startup - Siemens SIMATIC ET 200eco Manual

Distributed i/o station
Hide thumbs Also See for SIMATIC ET 200eco:
Table of Contents

Advertisement

4.2

ET 200eco commissioning and startup

Software requirements
Table 4-2

Software required for commissioning

Configuration
software used
STEP 7
COM PROFIBUS
Configuration software
for the DP master
used
Prerequisite for commissioning
Table 4-3

Prerequisite for commissioning the ET 200eco

1. The DP slave is installed
2. The PROFIBUS address is set at the DP slave
3. The DP slave is wired
4. The DP slave is configured
5. The power supply to the DP master is switched on
6. The DP master is set to RUN mode
Commissioning ET 200eco
Table 4-4

Steps for commissioning the DP slave

Step
1.
Switch on the electronic/sensor power supply to the DP slave.
2.
If required, switch on the load voltage supply.
ET 200eco Distributed I/O Station
A5E00158716-02
Version
V4.02 or higher
You have implemented the GSD file for ET 200eco in
STEP 7.
V 5.1 or higher;
The GSD file is included in the scope of delivery.
ServicePack 4
V3.0 or higher
You have implemented the GSD file for ET 200eco in
COM PROFIBUS.
You require the GSD file for ET 200eco.
Prior activity
Commissioning and diagnostics
Notes
Chapter 2
Chapter 2.6
Chapter 3
Chapter4.1
The DP master manual
The DP master manual
Procedure
See...
4-3