Commissioning

6.2 Commissioning on PROFIBUS DP

6.2
Commissioning on PROFIBUS DP
6.2.1

Configuring ET 200S on PROFIBUS DP

6.2.1.1

Basic principles of configuration for the ET 200S on PROFIBUS DP

Introduction
Configuration involves configuring and assigning parameters to the ET 200S.
● Configuration: The systematic arrangement of the different ET 200S modules (setup).
● Assigning parameters: Defining the ET 200S parameters with the configuration software.
Note
The ET 200S is included in the hardware catalog of HW Config:
• IM151-1 BASIC:
• IM151-1 COMPACT:
• IM151-1 STANDARD:
• IM151-1 FO STANDARD:
• IM151-1 HIGH FEATURE: from
You will not need a GSD file. Advantages:
• Simplified summary of the devices (via the "Pack addresses" button in HW Config)
• Validity checking of parameters
You can find further information about the procedure in the
DPV1 operation
If you are using IM151-1 STANDARD (6ES7151-1AA04-0AB0 or higher) in DPV1 mode on
an S7 CPU that does not support an insert/remove module interrupt, you must not enable
the "Operation at preset <> actual configuration" parameter in
removal of a module (module failure) always results in a station failure (OB 86).
If it is imperative that you enable "Operation at preset <> actual configuration", you must
either select DPV0 mode or configure IM151-1/FO STANDARD using the GSD file (under
"Additional field devices - I/O" in the
actual configuration" is then possible even when the insert/remove module interrupt is
disabled.
However, the S7-CPU does not register an insertion or removal (module failure). You can
detect such events only by cyclically reading the diagnostic frame and evaluating the module
status.
102
STEP 7
STEP 7
"ET 200S/COMPACT"
V5.2 and higher
V5.3 with Service Pack 3 or higher +HSP
STEP 7
V5.0 with Service Pack 3 or higher
STEP 7
V5.1 with Service Pack 1 or higher
STEP 7
V5.1 with Service Pack 3 or higher
STEP 7
hardware catalog). "Operation at preset <>
STEP 7
Online Help.
STEP 7.
Otherwise, the
Operating Instructions, 08/2008, A5E00515771-06
ET 200S