Commissioning
6.3 Commissioning on PROFINET IO
6.3.2

Assigning device names to the I/O device

Introduction
Each PROFINET IO device is assigned a unique device ID by the manufacturer
(MAC address).
For configuration and in the user program, each ET 200S IO device is addressed with its
device name.
For detailed information on addressing in PROFINET IO, refer to the
Description
Requirements
● IM151-3 Interface Module
● SIMATIC Micro Memory Card 64k and higher
● The PD must be online on PROFINET to the IO device to let you assign a device name to
● The IO device is configured in HW Config and assigned an IP address.
Assigning a device name
1. Insert an empty SIMATIC Micro Memory Card into the module slot on the front of the
2. Switch on the power supply for the IM151-3 PN.
3. Open the Properties - IM151-3 PN window in the HW Config or Properties - IM151-3 PN
Transferring the device name to the interface module
1. In HW Config select PLC > Ethernet > Assign Device Name.
2. Click the Assign name button in the Assign device name window.
Result
The device name is stored on the SIMATIC Micro Memory Card in the IM151-3 interface
module.
116
.
the interface module.
IM151-3.
HIGH FEATURE and enter the device name for the IO Device there and confirm with OK.
Do not use the device name "noname" (not case-sensitive).
PROFINET System
Operating Instructions, 08/2008, A5E00515771-06