Changing parameter settings using SIMATIC PDM

Note
For a complete list of parameters, see the Function Manual.
Clicking on Cancel during an upload from device to SIMATIC PDM will result in some
parameters NOT being updated.
Many parameters are accessed via the online menus in PDM, see Parameters accessed via
drop-down menus for the others.
1. Launch SIMATIC PDM, connect to the appropriate device and upload data.
2. Adjust parameter values in the parameter value field then click on Enter. The status fields
read Changed.
3. Open the Device menu, click on Download to device, then use File → Save to save settings
offline. The status fields are cleared.
182