Modbus communication
A.9 Modbus holding register tables
A.9.6

Setup

A.9.6.1

Sensor

Sensor settings
Table A-13
General sensor settings
Modbus
Data type /
register
Size in bytes
1801
Unsigned / 2
Pipe settings (clamp-on)
Table A-14
Pipe settings
Modbus
Data type /
register
Size in bytes
1200
Float / 4
1202
Float / 4
90
Parameter
Description
Flow direction
Define positive and
negative flow direction.
Default positive flow di‐
rection is indicated by
an arrow on the sensor.
Parameter
Description
Outer pipe di‐
External pipe diameter. 0.1
ameter
Wall thickness
Pipe wall thickness.
Default value
Value range /
[units]
Setting options
(units register)
1
● 0: Negative: The flow
is measured '+' in
default negative
direction and '-' in
default positive
direction.
● 1: Positive: The flow
is measured '+' in
default positive
direction and '-' in
default negative
direction.
Default value
Value range /
[units]
Setting options
(units register)
0.006 - 10.0
[m]
(8556)
0.001
1.0E-6 - 0.5
[m]
(8556)
Operating Instructions, 09/2017, A5E41425845-AB
Access
level
Read /
write
Access
level
Read /
write
Read /
write
FST020 IP65 NEMA 4X