Baxi POWER HT+ Series Installation, User And Service Manual page 58

Hide thumbs Also See for POWER HT+ Series:
Table of Contents

Advertisement

7 Installation
Fig.76
Through-roof flue system B
L1
L3
L2
Tab.20
Flue gas system connection type B
Arrangement
L3<2m + 2 elbows
L3<2m + 2 elbows
L3<5m + 2 elbows
L3<5m + 2 elbows
Fig.77
130 - 150 kW
L
1
3
4
L
Tab.21
Maximum length for configuration C
Configuration
Unit
mm
1
m
2
m
3
m
4
m
58
POWER HT +
23p
23p
Configuration
(L1 + L2) rigid
(L1 + L2) flexible
(L1 + L2) rigid
(L1 + L2) flexible
L
2
L
13
POWER HT+ 1.130
Ø 110
L < 8
L < 8
L < 7
L < 7
Important
For B
configurations, the lengths given in the tables are valid
23p
for horizontal pipes with a maximum length of 1 metre. For each
additional metre of horizontal pipe, subtract 1.2 m from the vertical
length L
.
max
Unit
POWER HT
+ 1.130
mm
Ø 110
m
20
m
7
m
17
m
-
Configuration C
13
Important
Pipes subject to technical evaluation 14 08–1289.
200 - 250 kW
L
1
3
POWER HT+ 1.150
Ø 110
L < 8
L < 8
L < 7
L < 7
POWER HT
POWER HT+
+ 1.150
1.200
Ø 110
Ø 160
27
39
9
19
23
36
6
15
L
2
4
L
L
POWER HT+ 1.200
POWER HT+ 1.250
Ø 160
Ø 160
L < 45
L < 22
L < 45
L < 22
L < 42
L < 19
L < 41
L < 18
7702630 - v02 - 11082018
POWER HT+
1.250
Ø 160
23
13
19
10

Hide quick links: