Cleaning The Siphon - Baxi POWER HT+ Series Installation, User And Service Manual

Hide thumbs Also See for POWER HT+ Series:
Table of Contents

Advertisement

Fig.165
L3
Fig.166
3
4
6
5
Fig.167
7702630 - v02 - 11082018
7. Check the distance between the ignition electrode and the ground
electrode.
Tab.67
Boiler model
POWER HT+ 1.130
POWER HT+ 1.150
POWER HT+ 1.200
POWER HT+ 1.250
8. Check there is no damage to the insulation on the inside surface of
the burner. The surface must be clean and free of any damage.
Replace the insulation if it is damaged.
9. Remount the burner.
11.2.5

Cleaning the siphon

POWER HT+ 1.130 and POWER HT+ 1.150
1. Remove the burner.
2. Access the siphon.
3. Disconnect the pipe leading from the rainwater holding tank.
4. Disconnect the condensate discharge pipe.
5. Remove the screw retaining the siphon.
6. Remove the siphon by pulling it towards you.
7. Clean the bottom of the siphon with water.
8. Completely fill the siphon.
9. Refit the siphon and fit the screw to hold the siphon in place.
10. Remount the burner.
Danger
Fill the siphon to the top. If the siphon is empty, there is a danger
of intoxication by exhaust gases.
POWER HT+ 1.200 and POWER HT+ 1.250
1. Open the spring clip retaining the siphon.
2. Remove the siphon by pulling it towards you.
3. Clean the bottom of the siphon with water.
4. Completely fill the siphon.
5. Refit the siphon and reattach the spring clip to hold the siphon in
place.
2
Danger
Fill the siphon to the top. If the siphon is empty, there is a danger
of intoxication by exhaust gases.
1
L3
11 Maintenance
Distances and tolerances to be
observed for the ignition elec­
trode and the ground electrode
(mm)
4.5 +/-0.5
4.5 +/-0.5
4.5 +/-0.5
4.5 +/-0.5
POWER HT +
115

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents