Connecting The Expansion Vessel; Connecting The Condensate Discharge Pipe - Baxi POWER HT+ Series Installation, User And Service Manual

Hide thumbs Also See for POWER HT+ Series:
Table of Contents

Advertisement

Fig.68
Tab.16
Volume of the expansion vessel in relation with the volume of heating circuit
Initial pressure of
the expansion ves­
100
sel
50 kPa
4.8
(0.5 bar)
100 kPa
8.0
(1 bar)
150 kPa
13.3
(1.5 bar)
Fig.69
2
7702630 - v02 - 11082018
5
MW-5000810-2
125
150
6.0
7.2
10.0
12.0
16.6
20.0
1
5. Fit the circulating pump on the heating return pipe (circulating pump
not provided).
7.3.2

Connecting the expansion vessel

1. Determine the volume of the expansion vessel according to the
volume of water in the heating circuit.
2. Connect the expansion vessel to the heating circuit return pipe.
Volume of the expansion vessel on the heating circuit
Volume of the installation (in litres)
175
200
250
8.4
9.6
12.0
14.0
16.0
20.0
23.3
26.6
33.3
Terms and conditions of validity:
Safety valve calibrated to 0.6 MPa (6 bar).
Average water temperature: 70°C.
Heating circuit flow temperature: 80°C.
Heating circuit return temperature: 60°C.
Filling pressure in the system lower than or equal to the initial pressure
in the expansion vessel.
7.3.3

Connecting the condensate discharge pipe

The condensate discharge pipe is located inside the boiler.
Do not block the condensate discharge pipe.
Set the discharge pipe at a gradient of at least 30 mm per metre,
maximum horizontal length 5 metres.
Do not drain condensation water into a roof gutter.
Connect the condensate discharge pipe in accordance with prevailing
standards.
It is preferable to use the condensate neutralisers recommended by the
manufacturer of the boiler.
1. Connect a plastic hose to the condensate discharge outlet (DN18) or
a rigid pipe (DN32).
2. Insert the other end of the hose into a waste water discharge outlet.
Important
Treat the condensate in accordance with prevailing local
regulations.
300
> 300
14.4
Volume of the installation x
0.048
24.0
Volume of the installation x
0.080
39.9
Volume of the installation x
0.133
POWER HT +
7 Installation
53