Venting Layout - Wall Mounted Vertical Exterior Power Vent - Montigo H36PVN Installation & Maintenance Manual

Power vent indoor gas fireplace
Table of Contents

Advertisement

H36PVN Power Vent Indoor Gas Fireplace
Installing a Wall Mounted Vertical Exterior Power Vent
(EDVWSPV58)
This section applies to installations where the shortest possible vent
run is through an exterior wall. Refer to Appendix A - Power Vent
locations, to ensure the planned Power vent location is acceptable.
Once the vent location has been established, please refer to the
appropriate section below for installation details.
Once the vent location has been established, please refer to the
appropriate section below for installation details.
Venting Layout - Wall Mounted Vertical Exterior
Power Vent
Selection of components and details of venting lay out should adhere
to the following guidelines:
■ Ensure there is a minimum run of 2' of straight pipe before
the power vent.
■ Ensure the maximum vent run does not exceed 100'.
■ Ensure the number of 90° elbows does not exceed 6.
■ Ensure the number of 45° elbows does not exceed 12.
V
Venting Installation
V + H (Maximum Length)
80 Feet
Figure 6. Typical Venting Installations.
Note: Images are shown without screens for clarity purposes.
However, your fireplace should not be operated without proper
installation of screens.
Page 14
Installation
H
Max. #
Elbows
6
Multi-Elbow Installations
Multi-elbow installations are possible up to a maximum of six
at 90° elbows.
Elbow 4
V2
Elbow 2
H1
V1
Elbow 1
Multi Elbow - Venting Installation
V1 + H1 + V2 + H2 + V3 = H3
(Maximum Length)
80 Feet
Figure 6a. Multi-elbow Venting Installations.
Downward Vertical Venting
Note: The downward vent run must not exceed 6' of vent run.
H1
V
Multi Elbow - Venting Installation
V1 + H1 + D + H2
(Maximum Length)
40 Feet
Figure 6b. Downward Venting Installations.
Elbow 6
H3
V3
Elbow 5
H2
Elbow 3
Max. #
Elbows
6
D
H2
Max. #
Elbows
6
XG0649 - 180130