Montigo H36PVN Installation & Maintenance Manual page 18

Power vent indoor gas fireplace
Table of Contents

Advertisement

H36PVN Power Vent Indoor Gas Fireplace
Installing an In-Line Linear Power Vent (LDVPV58)
This section applies to installations where an external roof
or wall mounted power vent is not aesthetically acceptable
or feasible.
Venting Layout
Selection of components and details of venting lay out should
adhere to the following guidelines:
Ensure there is a minimum run of 2' of straight pipe between
the fireplace and the power vent
Ensure the maximum vent run does not exceed 60'
Maximum vent run must be reduced by 10' for 1' of pipe
running in a vertical downward direction
Ensure the number of 90º elbows does not exceed 3 (maximum
allowable vent run must be reduced by 10' for every additional
90º elbow added)
Ensure the number of 45º elbows does not exceed 6
Linear Power Vent - Horizontal Termination
Example A. Vertical mounting with horizontal termination
Venting Installation
Maximum
Vent Run
60 Feet
** from fireplace to in-line power vent
Maximum allowable vent run must be reduced by ten feet (10'-0"
for every additional 90° elbow added. With a snorkel Termination,
reduce the total vent run by an additional twenty feet (20'-0"). Figure's
7 and 7a.
90deg
Elbow
Horizontal Run Flex Pipe
Vertical
Flex Pipe
Vertical Installed
Linear Power Vent
LDVPV58
2'-0 "
90deg
90deg
MIN
Elbow
Elbow
Figure 7. Vertical Mounting for the Linear Power Venter
CAUTION
■ Vent terminations can be very hot. The termination is to be installed higher than 7 feet
above a public walkway.
■ Do not obstruct, or attempt to conceal, the vent termination. These actions will affect the
operation of the fireplace, and may be hazardous.
■ In heavy snow areas, take extra care to prevent snow buildup from obstructing the vent
termination.
Page 18
Installation
Minimum
Max. #
Vent Run**
Elbows
2 Feet
3
Option
Option
Example B. Horizontal mounting with horizontal termination
Maximum
Vent Run
60 Feet
** from fireplace to in-line power vent
90deg
Elbow
Vertical
Flex Pipe
90deg
90deg
Elbow
Elbow
Figure 7a.
Horizontal Vent for the Linear Power Venter.
Example C. Horizontal mounting with downward vent run and
horizontal termination
Maximum
Vent Run
40 Feet
Termination
** from fireplace to in-line power vent
Maximum allowable vent run must be reduced by ten feet (10'-0")
for every additional 90° elbow added. Also, deduct ten feet (10'-0")
of vent length for every one foot (1'-0") of vent run traveling in a
downward direction.
Snorkel
Termination
Horizontal Installed
Linear Power Vent
LDVPV58
90deg
Elbow
Flush
Termination
VLWB-8
Figure 7b.
HorizontaI Linear Power Vent with Downward vent
and Horizontal Vent Run to Termination.
All venting material must be Montigo flex pipe, with as few joints
as possible. All joints use MVA vent splice. Montigo will not be
held responsible for any water damage that may occur from not
installing the equipment as specified by this document.
Note: Images are shown without screens for clarity purposes.
However, your fireplace should not be operated without proper
installation of screens.
Venting Installation
Minimum
Max. #
Vent Run**
Elbows
20 Feet
3
Horizonta
l
Insta
ll
e
d
Linear Power Vent
LDVPV58
Horizontal Run Flex Pipe
Option
Option
Venting Installation
Minimum
Max. #
Vent Run**
Elbows
2 Feet
3
90deg
Elbow
Vertical
Flex Pipe
Horizontal Run Flex Pipe
WARNING
Termination
Snorkel
Termination
Flush
Termination
VLWB-8
6'-0"
Max.
Termination
XG0649 - 180130