Advanced Commissioning; Enabling Functioning Of The External; Setting The K Coefficient Of The External Temperature Probe - Biasi Inovia 25S ERP User Manual And Installation Instructions

Wall hung, fanflue, roomsealed, high efficiency gas boiler
Hide thumbs Also See for Inovia 25S ERP:
Table of Contents

Advertisement

8

ADVANCED COMMISSIONING

8.1
Enabling functioning of the
external temperature probe by
the remote control
Functioning with the external probe in the
boiler must be enabled if the remote control
(optional) is used.
Act on the programming of the REMOTE con-
trol to enable its functioning if the remote con-
trol (optional) is used.
• Press button
for more than 3 seconds to
enter in
mode.
0
21
3
1
8
6
9
1 5
1
2
Fig. 8.1
Press buttons
and
to enter the transparent programming (Fig.
8.2).
Fig. 8.2
• Press buttons
"PM15" program that enables the external
probe (Fig. 8.3).
ADVANCED COMMISSIONING
at the same time
or
to display the
Fig. 8.3
• Modify the programmed SET by pressing
buttons
or
displayed, wait for the number programmed
to flash (Fig. 8.4).
Fig. 8.4
• To exit programming, press button .
8.2
Setting the K coefficient of the
external temperature probe
The boiler is set with a K coefficient equal to
zero for boiler functioning without the probe
connected.
If the boiler is NOT EQUIPPED with the re-
mote control (optional) refer to Fig. 8.5.
until a setting of 60 is
- 59 -