• It is possible to modify parameter 10 by
00=0s to 100=510s using keys 10 or 11
(each increase or reduction by a unit on
the display corresponds to 5 seconds). Ex.
36=180 seconds.
• The writing P10 - SEt alternates on the dis-
play (Fig. 8.25).
Fig. 8.25
• By pressing key 13 (Fig. 8.22) confirmation
of the inserted value is obtained.
• Press keys 16 or 17 (Fig. 8.22) to exit with-
out changing the value.
• Exiting the "programming mode" is auto-
matic, after 15 minutes, or by cutting power.
Programming using the REMOTE control
Act on the programming of the REMOTE con-
trol to select a minimum time between two ig-
nitions when the boiler functions in normal on/
off heating mode.
• Press button
for more than 3 seconds to
enter in
mode (Fig. 8.26).
0
21
3
1
8
6
9
1 5
1
2
Fig. 8.26
- 64 -
ADVANCED COMMISSIONING
• Press buttons
time to enter transparent programming (Fig.
8.27).
Fig. 8.27
• Press buttons
"PM10" program for selecting the ignition
frequency (Fig. 8.28).
Fig. 8.28
In Fig. 8.28 a SET programmed at 90 is dis-
played corresponding to a re-ignition time of
about 3 minutes.
The adjustment field is from 0 to 8 and half
minutes.
Each step increased or decreased corre-
sponds to 2 seconds.
• To modify the programmed SET, act on but-
tons
or
programmed to flash (Fig. 8.29).
and
at the same
or
to display the
and wait for the number