Calling Up And Resetting Service Messages - Viessmann VITODENS 200-W Installation And Service Instructions Manual

Type b2hb, b2kb, 1.8 to 35 kw wall mounted gas condensing boiler with vitotronic 200, weather-compensated natural gas and lpg version
Table of Contents

Advertisement

Commissioning, inspection, maintenance
Connecting the control unit to the LON
Boiler control unit
Control unit transmits the
time.
Parameter "7b:1"
Control unit transmits outside
temperature.
Set parameter "97:2".
Viessmann system number.
Parameter "98:1"
LON subscriber fault monitor-
ing.
Parameter "9C:20"
Carrying out a LON subscriber check
The subscriber check is used to test communication
with the system devices connected to the fault man-
ager.
Requirements:
The control unit must be activated as fault manager
(parameter "79:1" in the "General" group).
The LON subscriber number must be set in all con-
trol units.
The LON subscriber list in the fault manager must be
up to date.
Tap the following buttons:
1. "Menu" or
2. "Service"
3. Enter the password "viservice".
4. "Service functions"

Calling up and resetting service messages

Service indicator
Service limits can be set in conjunction with the com-
missioning assistant or via parameters "21" and "23" in
the "Boiler" group.
Once these values have been reached, a service mes-
sage appears on the display.
Tap the following buttons:
1. "Confirm"/
flashes in the footer.
52
Vitotronic 200-H
Control unit receives the
time.
Set parameter "81:3".
Control unit receives outside
temperature.
Set parameter "97:1".
Viessmann system number.
Parameter "98:1"
LON subscriber fault moni-
toring.
Parameter "9C:20"
(cont.)
Vitotronic 200-H
Control unit receives the
time.
Set parameter "81:3".
Control unit receives outside
temperature.
Set parameter "97:1".
Viessmann system number.
Parameter "98:1"
LON subscriber fault moni-
toring.
Parameter "9C:20"
5. "LON subscriber check"
The list of all connected LON subscribers appears.
6. Select subscriber and confirm with "OK"/
The subscriber check for the selected subscriber is
initiated.
If the subscriber check was successful, "Check OK"
is displayed.
If the subscriber check was unsuccessful, "Check
not OK" is displayed.
Note
To perform another subscriber check:
Create a new list of subscribers with "New list"/ .
The subscriber list is updated.
Note
During the subscriber check, the display of the relevant
subscriber shows the subscriber no. and "Wink" for
approx. 1 min.
2.
Note
If your heating system has several fault messages
simultaneously, the following will be displayed after
you tap
:
3. "Service, messages"
The service messages appear yellow in a list.
After maintenance has been carried out
Tap the following buttons:
1. "Menu" or "
"
Vitocom
Device receives the
time.
.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents