Viessmann VITODENS 200-W Technical Data Manual

Viessmann VITODENS 200-W Technical Data Manual

Gas-fired wall-mounted condensing boiler 31 to 370 mbh / 9 to 105 kw multi-boiler installation 320 to 1480 mbh/

Advertisement

VITODENS 200-W
Gas-fired wall-mounted condensing boiler
31 to 370 MBH / 9 to 105 kW
Multi-boiler installation 320 to 1480 MBH/
Technical Data Manual
Model Nos. and pricing: see Price List
Vitodens 200-W
WB2B Series
Gas-Fired Wall-Mounted Condensing Boiler
with modulating MatriX cylinder burner
for room air independent operation
(using a direct vent system) or room air
dependent operation
For Natural Gas and Liquid Propane Gas
Heating input
31 to 370 MBH
for NG and LPG
9 to 105 kW
5369 295 v1.2 08/2010
 This trademark is registered with the U.S. Patent and Trademark Office.

Advertisement

Table of Contents
loading

Summary of Contents for Viessmann VITODENS 200-W

  • Page 1 VITODENS 200-W   Gas-fired wall-mounted condensing boiler 31 to 370 MBH / 9 to 105 kW Multi-boiler installation 320 to 1480 MBH/ Technical Data Manual Model Nos. and pricing: see Price List Vitodens 200-W WB2B Series Gas-Fired Wall-Mounted Condensing Boiler...
  • Page 2: Product Information

    WB2B 105 only). Energy Star and the electronic adjustment. CSA Energy Performance are not applicable for model WB2B 105. HLasting performance with industry-leading Viessmann made SA240 316 Ti stainless steel Inox-Radial heat exchanger constructed to CSA B51 and ASME Section IV. HLow Emission Combustion with Viessmann made stainless steel MatriX cylinder burner.
  • Page 3 Cross-Section Inox-Radial heat exchanger Modulating MatriX cylinder burner Vitotronic 200, HO1 on-board outdoor reset control Boiler may not look exactly as illustrated.
  • Page 4: Technical Data

    Technical Data Table 1. Boiler Model Model No. WB2B- 105* Natural gas / Liquid propane gas 31-67 31-93 31-125 60-160 60-212 104-285 104-370 CSA input 9-20 9-27 9-37 17-47 17-62 30-83 30-108 28-61 28-85 28-114 55-146 55-194 95-260 98-350 CSA output/DOE 8-18 8-25 8-33...
  • Page 5 Requires 1” / 25 mm tubing. See the Installation Instructions of the Vitodens 200-W, WB2B for details. For side wall vent installations (coaxial system): Do not exceed max. equivalent length specified in the Installation Instructions of the Vitodens 200-W, WB2B Venting System. A maximum of 5 elbows may be installed in the vent system.
  • Page 6 Dimensional Information Models WB2B 19, 26, 35 17¾” / 6¼” / 158 mm 450 mm 12” / 300 mm ” / 2¾” / 143 mm 70 mm 33½” / 850 mm 78” / 1975 mm for single boiler installation 2¾” / 70 mm 2½”...
  • Page 7 Dimensional Information Models WB2B 45, 60 19” / 480 mm 6½” /165 mm 9½” / 240 mm 12” / 305 mm 5½” / 146 mm Ø 5” / 125 mm 39” / 51” / 996 mm 1301 mm 41¾” / 33½...
  • Page 8 Dimensional Information Models WB2B 80, 105 19” / 480mm 9½” / 9½” / 236mm 15¾” / 240mm 400mm “ / 295mm for WB2B 80-105 using the coaxial vent system 4¼” / 108mm 78” / 1975 mm for single boiler installation 9½”...
  • Page 9: Minimum Clearances

    0 0 AL, CL AL= Alcove CL= Closet Refer to the Installation Instructions of the Vitodens 200-W, WB2B Venting System for details. Please note: The Vitodens boiler has passed the zero inches vent clearance to combustibles testing requirements dictated by the Harmonized Standard ANSI Z21.13.
  • Page 10: Waterside Flow

    Use standard friction loss method for pipe sizing. Observe boiler maximum and minimum flow rate limitations. If system flow rate exceeds boiler maximum flow rate (as stated above), falls below the minimum flow rate or if system flow rate is unknown, Viessmann strongly recommends the installation of a low-loss header.
  • Page 11 Use standard friction loss method for pipe sizing. Observe boiler maximum and minimum flow rate limitations. If system flow rate exceeds boiler maximum flow rate (as stated above), falls below the minimum flow rate or if system flow rate is unknown, Viessmann strongly recommends the installation of a low-loss header.
  • Page 12 Heating Circuit / Boiler Pumps Viessmann offers a variety of Grundfos heating circuit / boiler pumps which meet typical Vitodens system installation requirements (see “Heating circuit pump (field supplied)“ or “Boiler pump (field supplied)” in the Installation Examples starting on page 29). See tables below for recommended pumps.
  • Page 13 Flow limitation L/h / GPM 8000 / 35.2 Table 10. Sizing of Low-Loss Header in a Residential Single-Boiler Application Boiler No. of Boiler Typical System Flow Rates Viessmann Model Boilers Max. Temp. Sensor Flow Rate Required ∆ ∆ ∆ ∆...
  • Page 14 200/120 200/120 NOTE: for multiple boiler applications when using the the Vitodens 200-W, WB2B boilers, refer to the multiple boiler low-loss distribution manifold installation instructions. For system ∆ ∆ ∆ ∆ t < 20°F use low-loss header sizes for ∆ ∆ ∆ ∆ t 20°F.
  • Page 15 DHW Production Domestic Hot Water Production Vitodens 200-W boilers can be used in conjunction with the stand-alone DHW storage tanks offered by Viessmann. All Viessmann DHW storage tanks sold in North America are available in “Vitosilver” finish only. Size and select the DHW storage tank based on the forecasted DHW consumption of the building in question.
  • Page 16 These advantages directly derive from the immediate availability of domestic hot water at all draw points. Poor insulation of the DHW recirculation line, however, can result in considerable heat loss. Viessmann therefore recommends that effective insulation be provided and used for DHW recirculation lines of 23 ft. / 7 m in length or longer.
  • Page 17: Wall Mounting

    Models WB2B 19, 26, 35 The Vitodens 200-W, models WB2B 19 to 35 comes with a template, which allows you to easily mark the location of the screws for the mounting bracket and the location of the flue gas pipe on the wall.
  • Page 18 Models WB2B 45, 60, 80, 105 The Vitodens 200-W, models WB2B 45 to105 comes with a template, which allows you to easily mark the location of the screws for the mounting bracket and the location of the flue gas pipe on the wall.
  • Page 19 (if applicable). Condensate Connection for Condensate Connection for Condensate Connection for Vitodens 200-W, models WB2B 19, 26, 35 Vitodens 200-W, models WB2B 45, 60 Vitodens 200-W, models WB2B 80, 105 Fig. 21 Fig. 23 Fig.
  • Page 20 Venting Options For an overview of venting options refer to the appendix starting on page 42. For detailed information refer to the Installation Instructions for the Vitodens 200-W, WB2B Venting System. Fig. 25 Vent Connection, models WB2B 45, 60, 80,105 Fig.
  • Page 21: Boiler Control

    Boiler Control Design and Functions Modular Structure Summer Operation The control unit contains: w“ H Auxiliary function for DHW heating Heating program “ System on/off switch, override/emission (short-term heating to a higher The burner is only activated upon a call for test switch, fixed high limit, adjustable high domestic hot water from the DHW storage temperature, gas fired central heating...
  • Page 22 Boiler Control Boiler Temperature Sensor Outdoor Temperature Sensor Heating Curve Adjustment (slope and shift) The boiler temperature sensor is connected The control unit regulates the boiler water at the control unit for weather-responsive temperature (= supply temperature of operation and is built into the boiler. heating circuit without mixing valve) and the Max.
  • Page 23 Fig. 29 (dimensions in mm) The mixing valve actuator is mounted Fig. 32 (dimensions in mm) Fig. 30 (dimensions in mm) directly on the Viessmann ¾ to 2½“ mixing Specification valve. Lead lenght 10 ft / 3.0 m, fully wired The mixing valve actuator is a motor-driven Installed with a strapping band.
  • Page 24 Vitotronic Control Accessories Vitotrol 200 Vitotrol 300 Room Temperature Sensor, Part No. 7450 017 Part No. 7248 907 Part No. 7133 379 Fig. 35 (dimensions in mm) Fig. 33 (dimensions in mm) Fig. 34 (dimensions in mm) KM BUS subscriber KM BUS subscriber The Vitotrol 300 remote control regulates Separate room temperature sensor as...
  • Page 25: Boiler Accessories

    Applications with neutralizing granulate (included in boiler technical literature set) Part No. 7134 230 The Vitodens 200-W, WB2B boiler comes (max. flow rate 17.6 GPM / 4 m factory set for operation with natural gas. –Type 120/80 for models WB2B 19, 26, 35 All WB2B models can be field converted to Part No.
  • Page 26 AB Air Bleed header ensures low return temperatures to BR Boiler Return the Vitodens 200-W boiler at all times, BS Boiler Supply increasing operational efficiency. BY Bypass (with laminar flow) In addition, the low-loss header helps...
  • Page 27 1.34 10.0 1.37 1.40 1.44 The Vitodens 200-W, WB2B boilers come equipped with Lambda Pro, the industry’s first intelligent combustion management system. The boiler adjusts automatically to any gas type and quality without the need for a fuel conversion kit.
  • Page 28: Installation Examples

    If a DHW storage tank other than a The examples on the following pages depict DHW supply and return piping between Viessmann Vitocell 100 or 300 tank is possible piping layouts of the Vitodens boiler DHW connections and the Viessmann...
  • Page 29 Installation Examples System Layout 1 Vitodens 200-W, WB2B with a direct-connected heating circuit Fig. 42 Legend Installation of ... AV Air vent (models WB2B 19 to 60 only) H radiator heating circuit (high-temp. circuit) IMPORTANT PRV Pressure relief valve H DHW production TPV Temperature and pressure relief valve ...
  • Page 30 Installation Examples System Layout 2 Vitodens 200-W, WB2B with a direct-connected heating circuit and low-loss header Fig. 43 Legend P Heating circuit pump IMPORTANT AV Air vent (models WB2B 19 to 60 only) PRV Pressure relief valve TPV Temperature and pressure relief valve...
  • Page 31 (low-temp. circuit) DHW circulating pump I must pump into H DHW production Vitodens 200-W WB2B boiler with the Vitodens 200-W WB2B boiler (as ... with the following flow conditions: Vitotronic 200, HO1 outdoor reset illustrated). The flow rate of the heating circuit is less...
  • Page 32 Radiator heating circuit IMPORTANT circuits is less than the maximum possible Heating circuit pump water flow rate of the Vitodens 200-W Mixing valve temperature sensor DHW circulating pump Q must pump into WB2B boiler (see page 10 for max. water...
  • Page 33 Kit for heating circuit with mixing valve DHW circulating pump Q must pump into possible water flow rate of the Vitodens Domestic hot water storage tank the Vitodens 200-W WB2B boiler (as 200-W WB2B boiler (see page 11 for DHW tank temperature sensor illustrated).
  • Page 34 . The second under floor heating circuit is low-loss header O DHW supply and return piping supplied by a field supplied circulation the Vitodens 200-W WB2B boiler (as P DHW circulating pump sK controlled by an accessory kit or a illustrated).
  • Page 35 Outdoor temperature sensor water flow rate of the Vitodens 200-W Remote control Vitotrol 300 (optional) IMPORTANT WB2B boiler (see page 11 for maximum Under floor heating circuit water flow rate of boiler).
  • Page 36 – DHW storage tank – low-loss header – multiple heating circuits with mixing valves Fig. 49 When designing a system as illustrated above, please contact your local Viessmann Sales Representative for assistance. DHW storage tank Legend IMPORTANT AV Air vent (WB2B models 19 to 60 only)
  • Page 37 Installation Examples System Layout 9 Multiple (up to four) Vitodens 200-W, models WB2B 45 to 105 with... – multiple heating circuits with mixing valves – low-loss header Vitocontrol-S Boiler 1 Boiler 2 Boiler 3 Boiler 4 Common Supply Temperature Sensor...
  • Page 38 *Note: When using a low loss header in the system, the DHW connections can be made downstream of the low loss header. See Vitodens 200-W WB2B Start-up/Service Instructions for applicable system coding information (see coding level 2): 00: ... A2: ...
  • Page 39: Wiring Diagram

    Wiring Diagram Overview of Electrical Connections, Models WB2B 19, 26, 35, 45 and 60 Power/Pump module MAIN POWER SUPPLY 120V, 60HZ, 12A MAIN DISCONNECT SWITCH 120/230 Transformer 1 2 3 1 2 3 1 2 3 120VAC L1 G N L G N WALL RECEPTACLE...
  • Page 40 Wiring Diagram Overview of Electrical Connections, Models WB2B 80 and 105 Power/Pump module MAIN POWER SUPPLY 120V, 60HZ, 12A MAIN DISCONNECT SWITCH 120/230 Transformer 1 2 3 1 2 3 1 2 3 120VAC L1 G N L G N WALL RECEPTACLE 120VAC...
  • Page 41: System Design Considerations

    Please certified together with the Vitodens 200-W observe that an antifreeze/water mixture Vitodens 200-W boilers can be used in any boiler as a constructional unit. may require a backflow preventer within the fully pumped hot water heating system.
  • Page 42 50-53 Page Sealed combustion, coaxial vent material to be supplied by Viessmann only. Stainless steel vent material must be ULC/UL listed, stainless steel AL29-4C® for Category IV boilers. Suggested sources: Flexmaster Canada Ltd. / Z-Flex (US) Inc., Heat-fab, ProTech Systems Inc., or Security Chimneys Int’l.
  • Page 43 Always follow Viessmann venting installation instructions. - Do not common vent Vitodens 200-W with any other appliance. - Layouts on the following pages are for illustrative purposes only. - Do not use Price List for installation purposes. This is not a design tool.
  • Page 44 Appendix Coaxial PPs Vent System Vent System Vent System Vent System Diameter Diameter 60/100 80/125 100/150 Maximum Equivalent Horizontally Vented WB2B -19/-26 -19/-26 -19/-26 Length (EqL) 33 / 10 43 / 13 52 / 16 ft. / m WB2B 26 / 8 36 / 11 49 / 15 ft.
  • Page 45 PPs coaxial vent material must be ULC S-636 certified for Category IV boilers. Do not mix non-ULC S-636 with ULC S-636 venting. Side wall venting installation must include Viessmann Protective Screen! Order 1 Mounting Clip for each straight length of vent pipe installed.
  • Page 46 Appendix Coaxial PPs Vent System (continued) Vent System Vent System Diameter Diameter 60/100 80/125 100/150 Maximum Equivalent Vertically Vented WB2B -19/-26 -19/-26 -19/-26 Length (EqL) 30 / 9 39 / 12 52 / 16 ft. / m WB2B -35/-45 23 / 7 33 / 10 49 / 15 ft.
  • Page 47 Do not include first 90° elbow in equivalent vent length calculations (this applies to all vent materials). " A maximum of 5 elbows may be installed in the vent system; do not exceed maximum equivalent vent length. " Always follow Viessmann venting installation instructions 5368 815.
  • Page 48 Appendix Stainless Steel Vent System Vent System Vent System Diameter Diameter 3” 4” Maximum Equivalent Horizontally Vented WB2B -19...-35 -19...-35 Length (EqL) a + b 148 / 45 180 / 55 ft. / m Room Air 1 Boiler Vent Adaptor included with boiler Independent Operation Independent Operation...
  • Page 49 Do not include first 87° elbow in equivalent vent length calculations (this applies to all vent materials). " A maximum of 5 x 90° elbows may be installed in the air intake and flue outlet combined; do not exceed maximum equivalent vent length. " Always follow Viessmann venting installation instructions 5368 815.
  • Page 50 Do not include first 87° elbow in equivalent vent length calculations (this applies to all vent materials). " A maximum of 5 x 90° elbows may be installed in the air intake and flue outlet combined; do not exceed maximum equivalent vent length. " Always follow Viessmann venting installation instructions 5368 815.
  • Page 51 Do not include first 87° elbow in equivalent vent length calculations (this applies to all vent materials). " A maximum of 5 x 90° elbows may be installed in the air intake and flue outlet combined; do not exceed maximum equivalent vent length. " Always follow Viessmann venting installation instructions 5368 815.
  • Page 52 Do not include first 87° elbow in equivalent vent length calculations (this applies to all vent materials). " A maximum of 5 x 90° elbows may be installed in the air intake and flue outlet combined; do not exceed maximum equivalent vent length. " Always follow Viessmann venting installation instructions 5368 815.
  • Page 53 Appendix I M P O R T A N T : Do not use any DWV plumbing pipes to vent this boiler. CPVC Vent System Vent System Vent System Diameter Diameter 2” 3” 4” Maximum Equivalent Horizontally Vented WB2B -19...-35 -19...-35 -19...-35 Length (EqL)
  • Page 54 Do not include first 90° elbow in equivalent vent length calculations (this applies to all vent materials). " " A maximum of 5 x 90° elbows may be installed in the air intake and flue outlet combined; do not exceed maximum equivalent vent length. " Always follow Viessmann venting installation instructions 5368 815.
  • Page 55 Appendix I M P O R T A N T : Do not use any DWV plumbing pipes to vent this boiler. CPVC Vent System (continued) Vent System Vent System Vent System Diameter Diameter 2” 3” 4” Maximum Equivalent Vertically Vented WB2B -19...-35 -19...-35...
  • Page 56 " Always follow Viessmann venting installation instructions 5368 815.
  • Page 57 Appendix I M P O R T A N T : Do not use any DWV plumbing pipes to vent this boiler. CPVC Vent System (continued) Vent System Vent System Diameter Diameter 3” 4” 4” Maximum Equivalent Horizontally Vented WB2B -45/-60 -45/-60 -80/-105...
  • Page 58 Do not include first 90° elbow in equivalent vent length calculations (this applies to all vent materials). " A maximum of 5 x 90° elbows may be installed in the air intake and flue outlet combined; do not exceed maximum equivalent vent length. " Always follow Viessmann venting installation instructions 5368 815.
  • Page 59 Do not include first 90° elbow in equivalent vent length calculations (this applies to all vent materials). " A maximum of 5 x 90° elbows may be installed in the air intake and flue outlet combined; do not exceed maximum equivalent vent length. " Always follow Viessmann venting installation instructions 5368 815.
  • Page 60 Appendix I M P O R T A N T : Do not use any DWV plumbing pipes to vent this boiler. CPVC or Stainless Steel Vent System Vent System Vent System Diameter Diameter 2” 3” 4” Maximum Equivalent Hybrid Vent System WB2B -19...-35 -19...-35...
  • Page 61 Do not include first 87° elbow in equivalent vent length calculations (this applies to all vent materials). " A maximum of 5 x 90° elbows may be installed in the air intake and flue outlet combined; do not exceed maximum equivalent vent length. " Always follow Viessmann venting installation instructions 5368 815.
  • Page 62 Appendix I M P O R T A N T : Do not use any DWV plumbing pipes to vent this boiler. CPVC or Stainless Steel Vent System (continued) Vent System Vent System Vent System Diameter Diameter 3” 4” 4” Maximum Equivalent Hybrid Vent System WB2B...
  • Page 63 Do not include first 90° elbow in equivalent vent length calculations (this applies to all vent materials). " A maximum of 5 x 90° elbows may be installed in the air intake and flue outlet combined; do not exceed maximum equivalent vent length. " Always follow Viessmann venting installation instructions 5368 815.
  • Page 64 Viessmann Manufacturing Company (U.S.) Inc. Viessmann Manufacturing Company Inc. 45 Access Road 750 McMurray Road Warwick, Rhode Island • 02886 • USA Waterloo, Ontario • N2V 2G5 • Canada Tel. (401) 732-0667 • Fax (401) 732-0590 Tel. (519) 885-6300 • Fax (519) 885-0887 www.viessmann-us.com •...