Assigning Heating Circuits To The Remote Control - Viessmann VITODENS 200-W Installation And Service Instructions Manual

Type b2hb, b2kb, 1.8 to 35 kw wall mounted gas condensing boiler with vitotronic 200, weather-compensated natural gas and lpg version
Table of Contents

Advertisement

Control functions
(cont.)
Example using the settings in the delivered condition
C
D
B
60
50
40
30
30
20
10
A
0
6
7
Time
Fig. 80
Start of operation with standard room temperature
A
Set boiler water or flow temperature in accordance
B
with the selected heating curve

Assigning heating circuits to the remote control

The assignment of heating circuits must be configured
during remote control commissioning.
Remote control affects the following heating circuit:
Heating circuit without mixer A1
Heating circuit with mixer M2
Heating circuit with mixer M3
Note
One heating circuit can be assigned to the Vitotrol 200-
A and 200-RF.
Up to 3 heating circuits can be assigned to the Vitotrol
300-A and 300-RF.
A maximum of 2 hardwired remote control units or 3
wireless remote controls may be connected to the con-
trol unit.
If the assignment of a heating circuit is later cancelled,
reset parameter A0 in the "Heating circuit" group for
this heating circuit to 0 (fault message bC, bd, bE).
8
9
Set boiler water temperature or set flow tempera-
C
ture in accordance with parameter FA:
50 °C + 20 % = 60 °C
D
Duration of operation with higher set boiler water
temperature or set flow temperature in accordance
with parameter Fb:
60 min
Configuration
Vitotrol 200-A
Vitotrol 200-RF
H 1
H 2
H 3
Function description
Vitotrol 300-A
Vitotrol 300-RF
Heating circuit 1
Heating circuit 2
Heating circuit 3
151