Installation sequence
Electrical connections

Connecting the Vitoconnect 100 connecting cable (accessories)

3.
Fig. 12
Installing the Vitoconnect 100
Vitoconnect 100 installation and commissioning
instructions

External demand via switching contact

Connection options:
EA1 extension (accessory, see separate installation
instructions)
Plug
lH
When the contact is closed, burner operation is load-
dependent. The boiler water is heated to the value set
in parameter "9b" in the "General" group. The boiler
water temperature is limited by this set value and the
electronic maximum limit (parameter "06" in the
"Boiler" group).
20
(cont.)
2.
1.
!
Please note
Live contacts lead to short circuits or phase fail-
ure.
The external connection must be potential-free
and meet the requirements of protection class II.