Filling The Trap With Water; Filling The Heating System - Viessmann VITODENS 200-W Installation And Service Instructions Manual

Type b2hb, b2kb, 1.8 to 35 kw wall mounted gas condensing boiler with vitotronic 200, weather-compensated natural gas and lpg version
Table of Contents

Advertisement

Filling the trap with water

Multi boiler system:
Fill the trap in the flue gas header with water as well.
A
B
Fig. 17
1. Remove supply hose
2. Remove trap
.
B
3. Fill trap
with water.
B

Filling the heating system

Fill water
According to EN 1717 with DIN 1988-100, as a heat
transfer medium for DHW heating, the heating water
must meet fluid category ≤ 3. This requirement is met if
water of potable quality is used as heating water. For
example, if additives are used, the additive manufac-
turer must specify which category the treated heating
water comes under.
Total permissible hardness of the fill and top-up water
Total heating output
kW
50
50 to
200
>
.
A
Specific system volume
< 20 l/kW
3.0 mol/m
3
(16.8 °dH)
2.0 mol/m
3
(11.2 °dH)
Commissioning, inspection, maintenance
4. Refit trap
.
B
5. Reconnect supply hose
Note
Never twist the supply hose during assembly.
!
Please note
Unsuitable fill water increases the level of
deposits and corrosion and may lead to appli-
ance damage.
Flush the heating system thoroughly before
filling.
Only use fill water of potable water quality.
Special antifreeze suitable for heating systems
can be added to the fill water. The antifreeze
manufacturer must verify its suitability.
Fill and top-up water with a water hardness in
excess of the following values must be soft-
ened, e.g. with a small softening system for
heating water.
20 l/kW to < 50 l/kW
2.0 mol/m
3
(11.2 °dH)
1.5 mol/m
3
(8.4 °dH)
.
A
50 l/kW
< 0.02 mol/m
3
(0.11 °dH)
< 0.02 mol/m
3
(0.11 °dH)
27