S5-115F Manual
Error
Con-
Error Message Text
Identi-
sec.
fier
No.
Progr.
109
01
LPB/LPW operation on non-
configured module:
Programming error
Additional info. 1:
Input byte/word No.
109
02
Long discrepancy time for
LPB/LPW operation not
permissible: configuration
error
Additional info. 1:
Input byte/word No.
EWA 4NEB 811 6149-02
Possible Cause
Error group No. 12
Word address of non-configured
module, decimal display
Error group No. 14
-
No direct access (L PB 0 to 127, L
PW 0 to 126) is permitted for the
specified DI byte, since a long
discrepancy time has been
configured
Word address of the non-configured
module, decimal display
PLC Error Messages
Remedy
-
Check address in user
program
Warm restart:
1. Stop/Run
-
Change configuration:
Configure DI byte with
shorter discrepancy time
-
Change user program:
Program PII access
(L IB 0 to 127, L IW 0 to 126)
Warm restart:
1. Stop/Run
B-67