PLC Error Messages
Error
Con-
Error Message Text
Identi-
sec.
fier
No.
Progr.
55
01
I/O modules cannot be
accessed:
I/O module or IM error
Additional info. 1:
I/O word No.
55
02
SINEC L1 LAN cannot be
operated:
CPU error
Additional info. 1:
Subunit
Additional info. 2:
Source slave number
B-48
Possible Cause
Error group No. 19
QVZ during access of I/O module (self-
test):
-
Module defective
-
Wrong address on the IM306
-
IM306 defective
Word address containing the QVZ,
decimal display
Error group No. 01
Source-slave-specific monitoring time
counter of the SINEC L1 LAN does not
correspond to the inverse time
counter
S5-115F Manual
Remedy
-
Replace module
-
Check addressing
-
Replace IM306
Warm restart:
1. Stop/Run
-
Replace module
Warm restart:
1. POWER OFF/ON
2. Stop/Run
EWA 4NEB 811 6149-02