Error
Con-
Error Message Text
Identi-
sec.
fier
No.
Progr.
102
10
I/O module error or
component structure error
102
11
Standard block too large:
User EPROM error
Additional info. 1:
Block type
Additional info. 2:
Block No.
Additional info. 3:
Initial address
102
12
Signature error in standard
block: user EPROM error
Additional info. 1:
Block type
Additional info. 2:
Block No.
Additional info. 3:
ACTUAL signature
EWA 4NEB 811 6149-02
Possible Cause
Error group No. 19
PEU signal active during structuring
of the 9th track:
-
Power failure in I/O expansion
unit
-
Connection with expansion unit
interrupted
-
Connector in central processor
missing
Error group No. 6
Standard block defective
Error group No. 16
Generated standard block signature
differs from signature read
Generated signature
Hex display
PLC Error Messages
Remedy
-
Check power supply in
expansion unit
-
Check connection
-
Plug terminating resistor into
central controller
Warm restart:
1. Stop/Run
-
Check standard block
Warm restart:
1. Stop/Run
-
Load prototype-tested
standard block
Warm restart:
1. Stop/Run