PLC Error Messages
Error
Con-
Error Message Text
Identi-
sec.
fier
No.
Progr.
100
01
User memory submodule for
S5-115F not permissible:
Handling error
Additional info. 1:
Submodule identifier
100
02
Wrong response to power
failure:
PS or CPU HW error
100
03
Subunit identifier for test
mode with RAM is missing:
Operating system awaits
input
Additional info. 1:
Subunit identifier found
100
04
Subunit identifier in EPROM/
EEPROM submodule missing:
Handling error or PG error
Additional info. 1:
Subunit identifier found
B-54
Possible Cause
Error group No. 30
-
Wrong EPROM submodule
plugged in
Submodule identifier of the
submodule used, hex display
Error group No. 01
Power failure did not trigger in-
terrupt service routine for power
failure with NAU signal
-
PS defective
-
CPU HW error
Error group No. 31
-
Subunit identifier not yet
entered
Wrong subunit identifier found,
hex display.
Error group No. 30
-
Subunit identifier not present in
user submodule or defective
-
Wrong user submodule used
-
COM 115F error
Wrong subunit identifier found,
hex display.
S5-115F Manual
Remedy
-
Exchange EPROM submodule
in PLC
Warm restart:
1. POWER OFF/ON
2. Stop/Run
-
Replace PS
-
Replace CPU
Warm restart:
1. POWER OFF/ON
2. Stop/Run
-
Enter subunit identifier using
COM 115F
Warm restart:
Not necessary
-
Rewrite EPROM
-
Service
Warm restart:
1. POWER OFF/ON
2. Stop/Run
EWA 4NEB 811 6149-02