Siemens SIMATIC S5 Manual page 273

Hide thumbs Also See for SIMATIC S5:
Table of Contents

Advertisement

S5-115F Manual
Error
Con-
Error Message Text
Identi-
sec.
fier
No.
Progr.
26
01
Error during RAM comparison
of A and B:
CPU error
Additional info. 1:
RAM address
Additional info. 2:
RAM byte in A
Additional info. 3:
RAM byte in B
26
02
Error during RAM test:
CPU error
Additional info. 1:
Initial address test area
26
03
Error during RAM test:
CPU error
Additional info. 1:
RAM address inverse location
Additional info. 2:
Contents of original location
Additional info. 3:
Contents of inverse location
26
04
Error during comparison
µP 8032 RAM and EPROM:
CPU error
EWA 4NEB 811 6149-02
Possible Cause
Error group No. 15
-
Memory location defective
-
One-sided overwrite of memory
location by the 115F operating
system
RAM address with different contents
in A and B,
hex display
Contents of the above-named RAM
location in A,
hex display
Contents of the above-named RAM
location in B,
hex display
Error group No. 13
-
Wrong initial address of the
current RAM test signal
Error group No. 07
Falsification of inverse double data
(non-inverse together)
-
CPU error
-
Overwriting of the original or
inverse data item by the 115F
operating system
Error group No. 13
-
SINEC L1 structure identifier
FIR bus contradicts configured
SINEC L1 structure
PLC Error Messages
Remedy
-
Replace CPU
-
Service
Warm restart:
1. OVERALL RESET
-
Replace CPU
-
Service
Warm restart:
1. POWER OFF/ON
2. Stop/Run
-
Replace CPU
-
Service
Warm restart:
1. POWER OFF/ON
2. Stop/Run
-
Replace module
Warm restart:
1. POWER OFF/ON
2. Stop/Run
B-13