Error
Con-
Error Message Text
Identi-
sec.
fier
No.
Progr.
27
01
Error during PL self-test:
PL error
Additional info. 1:
Page No.
Additional info. 2:
Memory address
Additional info. 3:
Current test background
27
02
Error during PL self-test:
PL error
Additional info. 1:
Page No.
Additional info. 2:
Memory address
Additional info. 3:
Current test background
Additional info. 4:
Current check pattern
27
03
Error during PL self-test:
CPU error
Additional info. 1:
Initial address
B-14
Possible Cause
Error group No. 04
PL error during read-after-write-
check of test section of current check
background:
-
PL defective
-
CPU HW error
Error group No. 04
PL error during read-after-write-
check of the page byte to be tested
-
PL defective
-
CPU HW error
Error group No. 13
Wrong initial address of current test
section:
-
CPU error
S5-115F Manual
Remedy
-
Replace PL
-
Replace CPU
Warm restart:
1. POWER OFF/ON
2. Stop/Run
-
Replace PL
-
Replace CPU
Warm restart:
1. POWER OFF/ON
2. Stop/Run
-
Replace CPU
Warm restart:
1. POWER OFF/ON
2. Stop/Run