If you have configured a SINEC L1 LAN in the basic menu for "Setting 115F Communications
Parameters", press function key F2.
F2 SIN-MAIL
The "SINEC L1 interface" screen form appears with the partner matrices (0: master, 1 to 30:
slave, 31: broadcast) of the Send and Receive mailboxes.
SINEC L1 INTERFACE
0 = MASTER
SEND
TO NODE
RECEIVE
FROM NODE
MAILBOX DB OR FLAG (D/F)
MAILBOX LENGTH IN BYTES (1 TO 62):48 QB DATA WORD (0 TO 255): 4
F1
MAILBOX
Figure 1-8. Screen Form for SINEC L1 Interface (Mailbox Table)
Use the cursor control keys to select the desired node.
The relevant mailbox table will be displayed provided it has already been selected once.
'***' will appear at those positions where the node numbers correspond to the slave
numbers.
F1 Select a node
F3 Deselect a node
If a node has been selected, the cursor will jump to the 'Mailbox table' field. Enter the
relevant mailbox address (DB or flag) and length here.
The following can be selected in this way:
Single LAN
Redundant LAN:
Note
If you have assigned parameters for high-level protection of the destination slave
number or monitoring for recognition of a change of message, please note when
filling in the form that the mailbox must be two bytes longer than your net data
( Vol 1, 7.2.2 of the Manual).
EWA 4NEB 811 6149-02
SINEC L1
1 TO 30 = SLAVE
1
***
3
16
***
Send mailbox table
F2
F3
F4
C MAILBOX
- up to 30 nodes (incl. master) with one Send mailbox each
- up to 30 nodes (incl. master) with one Receive mailbox each
- up to 14 nodes with one Send mailbox each and one master with two
Send mailboxes
- up to 15 nodes (incl. master) with two Receive mailboxes each
COM 115F / PDC15
SLAVE 2
31 = BROADCAST
NODE: 1
:D
DB_NO.
F5
F6
Configuring with COM 115F
xxx
(4 TO 255):50
F7
F8
RETURN
1-17