Siemens SIMATIC S5 Manual page 285

Hide thumbs Also See for SIMATIC S5:
Table of Contents

Advertisement

S5-115F Manual
Error
Con-
Error Message Text
Identi-
sec.
fier
No.
Progr.
30
07
Self-test in A and B not
synchronous: CPU error
Additional info. 1:
FXTE ZEI2 L in A
Additional info. 2:
FXTE ZEI2 L in B
30
08
Self-test in A and B not
synchronous: CPU error
Additional info. 1:
FITEKO OK in A
Additional info. 2:
FITEKO OK in B
30
09
Self-test in A and B not
synchronous: CPU error
Additional info. 1:
FXAE BLOCK ADR H in A
Additional info. 2:
FXAE BLOCK ADR H in B
EWA 4NEB 811 6149-02
Possible Causes
Error group No. 13
Test pointer 2 (FXTE ZEI2 L) is not
identical in A and B.
-
CPU error (one-sided overwrite
of memory location)
Error group No. 13
One subunit has completed
processing of test components in the
PC self-test (FITEKO OK = 1), while
the other subunit is still processing
test components (FITEKO OK = 0).
-
CPU error (one-sided overwrite
of memory location)
Error group No. 13
The FXAE BLOCK ADR H datum is not
identical in A and B
-
CPU error (one-sided overwrite
of memory location)
PLC Error Messages
Remedy
-
Replace CPU
-
Service
Warm restart:
1. POWER OFF/ON
2. Stop/Run
-
Replace CPU
-
Service
Warm restart:
1. POWER OFF/ON
2. Stop/Run
-
Replace CPU
-
Service
Warm restart:
1. POWER OFF/ON
2. Stop/Run
B-25

Advertisement

Table of Contents
loading

This manual is also suitable for:

S5-115f

Table of Contents