SiBE121021_C
1.2
Removal of Electrical Box
Procedure
Step
1. Disconnect the
harnesses.
Layout of the
1
connecting wires
Removal Procedure
Warning
Be sure to wait for 10 minutes or more after turning off all power
supplies before disassembling work.
Procedure
Electrical
box
Electronic expansion
valve coil
Liquid
pipe
Liquid stop valve
A port
B port
Service
monitor
PCB
C port
Wiring fixture
A port
B port
C port
(R11175)
Service port
Gas pipe
Gas stop valve
(R11176)
Terminal
board
Earth
Earth
wires
(R11177)
Outdoor Unit - 50~75 Class
Points
Illustrations are for 3 room
models as representative, 4
room models also have D
port.
Connecting wires
(1) Black :
Power supply
(2) White :
Power supply
(3) Red :
Transmission
Power Supply wires
(L) - Black
(N) - White
The wires are fixed to the
terminal board with screws.
375