4.3.5 Compressor Protection Function
When turning the compressor from OFF to ON, the upper limit of frequency is set as follows.
(The function is not used when defrosting.)
4.4

Discharge Pipe Temperature Control

Outline
The discharge pipe temperature is used as the internal temperature of the compressor. If the
discharge pipe temperature rises above a certain level, the upper limit of frequency is set to
keep this temperature from going up further.
Detail
Function and Control
(Hz)
Frequency
C
B
A
A (Hz)
B (Hz)
C (Hz)
D (seconds)
E (seconds)
F (seconds)
A
B
Discharge pipe
temperature
A (˚C)
B (˚C)
C (˚C)
D (˚C)
E (˚C)
Zone
Stop zone
When the temperature reaches the stop zone, the compressor stops.
Drooping zone
The upper limit of frequency decreases.
Keep zone
The upper limit of frequency is kept.
Reset zone
The upper limit of frequency is canceled.
D
E
F
50/52/58 class
68/75/80/90 class
55
70
85
150
120
180
200
300
470
Stop zone
Drooping
zone
C
Keep
zone
D
Reset zone
50/52/58 class
68/75/80/90 class
110
103
102
100
95
Control
Control Specification
(sec.)
Time
(R13528)
55
65
80
E
(R14266)
120
111
109
107
107
117