Outdoor Unit Pcb Abnormality - Daikin Super Multi NX FFQ25B8V1B Service Manual

E-series, f-series, g-series
Hide thumbs Also See for Super Multi NX FFQ25B8V1B:
Table of Contents

Advertisement

SiBE121021_C
7.2

Outdoor Unit PCB Abnormality

E1
Remote
Controller
Display
Outdoor Unit LED
A
Display
Method of
Detect within the program of the microcomputer.
Malfunction
Detection
Malfunction
The program of the microcomputer is in abnormal running order.
Decision
Conditions
Supposed
Causes
Troubleshooting
Power on again
Check to see that the unit is
grounded.
Service Diagnosis
j
i
i
i
1
2
3
4
Noise
Momentary fall of voltage
Momentary power failure
Defective outdoor unit PCB
Be sure to turn off the power switch before connecting or disconnecting
Caution
connectors, or parts may be damaged.
Error again?
NO
Grounded?
YES
h
h
5
YES
NO
Troubleshooting for Outdoor Unit
Replace the outdoor unit PCB.
Carry out grounding work.
The cause can be external
factors other than malfunction.
Investigate the cause of noise.
(R7183)