Field Settings
BRC1E51A7
a
a Unit No.
b First code No.
c Second code No.
d Mode
452
d
Step
Action
1
Press and hold the [Cancel] button (
for 4 seconds to enter the Field setting
menu.
2
Use the
buttons to select Field
setting list and push the [Menu/Enter]
button (
).
3
Use the
buttons to select the desired
Mode.
4
During group control, when setting by each
indoor unit (Mode 20, 21, 22 and 23 have
been selected), push the
highlight and
INDOOR UNIT NO. to be set. This
operation is unnecessary when setting by
group.
5
Highlight the second code No. to be
changed using the
the
buttons to select the desired
second code No.
6
Push the [Menu/Enter] button (
display the confirmation screen.
7
Use the
buttons to select Yes and push
the [Menu/Enter] button (
8
Push the [Cancel] button (
return to basic screen.
c
(R12878)
)
button to
buttons to select the
buttons, and use
) to
).
) 2 times to
SiBE121021_C
Remote controller
(R12879)
When setting by group, all of the
second code No. that may be set are
displayed as "*".
When multiple setting changes are
needed, repeat steps 3 to 7.