SET0102020

1.2.2 Configuration and setting information

"Table 1.2.2" lists the information to be obtained in advance from the sales representative or SE in
charge.
Verify the information got in advance.
Configuration and setting information
Installation Instructions Sheet
SET0103000

1.3 Checking Installation Requirements

This section describes requirements for installing the Base Unit.
If you find any problems, contact the related department and take appropriate action.
SET0103010

1.3.1 Environmental requirements

Confirm that the environmental requirements for installing the system fall within the range listed in
"Table 1.3.1-1".
To make sure the operating environments are satisfied, check them when the system is operating.
Operating
Temperature
[
C]
o
5 to 35 (without ATD)
5 to 40 (with ATD)
ANNT) The temperature requirements depend on the altitude of the installation location.
- When the system is installed at an altitude of 0 to 1000 m (0 to 3,281 ft.) above sea
level: 5 to 40
- When the system is installed at an altitude of 1,000 to 1,500 m (3,281 to 4,921 ft.) above sea
level: 5 to 38
- When the system is installed at an altitude of 1, 500 to 2,000 m (4, 921 to 6,562 ft.) above sea
level: 5 to 36
- When the system is installed at an altitude of 2,000 to 3, 000 m (6,562 to 9, 843 ft.) above sea
level: 5 to 33
The service engineer department should make the following checks related to environmental
requirements.
If there is a problem with the installation environment, ask the customer to implement the required
improvements.
- Measure items related to the installation environment (humidity and leakage current).
- Check the installation conditions (location, computer room, power supply facility,
and air conditioning).
- Confirm that the cold air flow from air conditioning and the hot equipment exhaust do not collide,
Table 1.3.1-1 System environmental requirements
Humidity
[%RH]
20 to 80
C (41 to 104.0
F)
o
o
C (41 to 100
F)
o
o
C (41 to 96.8
F)
o
o
C (41 to 91.4
F)
o
o
Table 1.2.2
Remarks
This sheet provides such customer-specified information as
IP addresses and passwords provided through sales/SE
departments.
Non-operating
Temperature
[
C]
o
0 to 50
15
Humidity
[%RH]
8
to 80

Advertisement