Using the Keypad Devices

The X200 Series inverter front keypad contains all the elements for both monitoring
and programming parameters. The keypad is layout is pictured below. All other
programming devices for the inverter have a similar key arrangement and function.
Key and Indicator Legend
• Run/Stop LED – ON when the inverter output is ON and the motor is developing
• Program/Monitor LED – This LED is ON when the inverter is ready for parameter
• Run Key Enable LED – is ON when the inverter is ready to respond to the Run key,
• Run Key – Press this key to run the motor (the Run Enable LED must be ON first).
• Stop/Reset Key – Press this key to stop the motor when it is running (uses the
• Potentiometer
• Potentiometer Enable LED – ON when the potentiometer is enabled for value entry.
• Parameter Display – A 4-digit, 7-segment display for parameters and function codes.
• Display Units, Hertz/Amperes – One of these LEDs will be ON to indicate the units
• Power LED – This is ON when the power input to the inverter is ON.
• Alarm LED – ON when an inverter trip is active (alarm relay contact will be closed).
• Function Key – This key is used to navigate through the lists of parameters and
• Up/Down keys – Use these keys alternatively to move up or down the lists of
• Store key – When the unit is in Program Mode and you have edited a parameter
More user manuals on
Display Units (Hertz / Amperes) LEDs
Parameter Display
Run key Enable LED
Run key
Stop/Reset key
Function key
torque (Run Mode), and OFF when the inverter output is OFF (Stop Mode).
editing (Program Mode). It is OFF when the parameter display is monitoring data
(Monitor Mode).
OFF when the Run key is disabled.
Parameter F004, Keypad Run Key Routing, determines whether the Run key
generates a Run FWD or Run REV command.
programmed deceleration rate). This key will also reset an alarm that has tripped.
– Allows an operator to directly set the motor speed when the
potentiometer is enabled for output frequency control.
associated with the parameter display.
functions for setting and monitoring parameter values.
parameter and functions shown in the display, and increment/decrement values.
value, press the Store key to write the new value to the EEPROM.
ManualsBase.com
POWER
Hz
ALARM
A
RUN
STOP
RUN
RESET
PRG
FUNC
2
STR
1
Up/Down keys
Store key
Power LED
Alarm LED
Run/Stop LED
Potentiometer Enable LED
Potentiometer
Program/Monitor LED