Hitachi X200-002SFE/NFU Instruction Manuals page 254

X200 series. single-phase input 200v class. three-phase input 200v class. three-phase input 400v class.
Table of Contents

Advertisement

Func.
Code
A051
A052
A053
A054
A055
A056
A061
A261
A062
A262
A063,
A065,
A067
A064,
A066,
A068
More user manuals on
Name
R/W
DC braking enable
R/W Two options; select codes:
DC braking frequency
R/W The frequency at which DC
setting
DC braking wait time
R/W The delay from the end of
DC braking force for
R/W Level of DC braking force,
deceleration
DC braking time for
R/W Sets the duration for DC
deceleration
DC braking / edge or
R/W Two options; select codes:
level detection for [DB]
input
Frequency upper limit
R/W Sets a limit on output frequency
setting
Frequency upper limit
R/W Sets a limit on output frequency
setting, 2nd motor
Frequency lower limit
R/W Sets a limit on output frequency
setting
Frequency lower limit
R/W Sets a limit on output frequency
setting, 2nd motor
Jump (center)
R/W Up to 3 output frequencies can be
frequency setting
Jump (hysteresis)
R/W Defines the distance from the
frequency width
setting
ManualsBase.com
List of Holding Registers
Description
00...Disable
01... Enable
02... Frequency detection
braking begins, range is from the
start frequency (B082) to 60 Hz
controlled deceleration to start of
DC braking (motor free runs
until DC braking begins),
range is 0.0 to 5.0 sec.
settable from 0 to 100%
braking, range is 0.0 to 60.0
seconds
00... Edge detection
01... Level detection
less than the maximum
frequency (A004). Range is from
frequency lower limit (A062) to
maximum frequency (A004).
0.0.. setting is disabled
>0.1 setting is enabled
less than the maximum
frequency (A204). Range is from
frequency lower limit (A262) to
maximum frequency (A204).
0.0.. setting is disabled
>0.1 setting is enabled
greater than zero.
Range is start frequency (B082)
to frequency upper limit (A061)
0.0 setting is disabled
>0.0 setting is enabled
greater than zero.
Range is start frequency (B082)
to frequency upper limit (A261)
0.0 setting is disabled
>0.0 setting is enabled
defined for the output to jump
past to avoid motor resonances
(center frequency)
Range is 0.0 to 400.0 Hz
center frequency at which the
jump around occurs
Range is 0.0 to 10.0 Hz
B−27
Network Data
Reg.
Range
Res.
1051h
0, 1, 2
1052h (B082 x 10)
0.1 Hz
to 600
1053h
0 to 50
1054h
0 to 100
1 %
1055h
0 to 600
0.1 sec
1056h
0, 1
105Ah (A062 x 10)
0.1 Hz
to (A004 x
10),
0=disable
>1=enable
1517h (A262 x 10)
to (A204 x
10),
0=disable
>1=enable
105Bh (B082 x 10)
0.1 Hz
to (A061 x
10),
0=disable
>1=enable
1518h (B082 x 10)
to (A261 x
10),
0=disable
>1=enable
105Dh
0 to 4000
0.1 Hz
1060h
1063h
105Eh
0 to 100
0.1 Hz
1061h
1064h

Advertisement