B089: Monitor display select for networked inverter – When the X200 inverter is
controlled via network, the inverter's keypad display can still provide Monitor Mode.
The D00x parameter selected by function B089 sill be displayed on the keypad. See
"Local Monitoring During Network Operation" on page 3-8
B092: Cooling Fan Control – You can select the performance of the cooling fan (if your
inverter has the fan) whether it stops or keep on running, after the inverter stops the
motor. This can result in an additional energy saving.
Func.
Code
B089
B092
More user manuals on
"B" Function
Name /
SRW Display
Monitor display select for
networked inverter
PANEL
d001
Cooling fan control
FAN-CTRL
OFF
ManualsBase.com
Description
Selects the parameter displayed on the
keypad display when the inverter is
networked, 7 options:
01...Output frequency monitor
02...Output current monitor
03...Rotation direction monitor
04...Process variable (PV), PID
feedback monitor
05...Intelligent input terminal status
06...Intelligent output terminal status
07...Scaled output frequency monitor
Selects when the fan is ON per inverter
operation, three options:
00...Fan is always ON
01...Fan is ON during run, OFF during
stop (5 min. delay from ON to OFF)
02...Fan is temperature controlled
for more details.
Run
Defaults
Mode
-FE
-FU
Units
Edit
(EU)
(USA)
01
01
00
00