The protection method conforms to JEM 1030.
The applicable motor refers to Hitachi standard 3-phase motor (4p). When
using other motors, care must be taken to prevent the rated motor current
(50/60Hz) from exceeding the rated output current of the inverter.
The output voltage decreases as the main supply voltage decreases (except
when using the AVR function). In any case, the output voltage cannot exceed
the input power supply voltage.
To operate the motor beyond 50/60Hz, consult the motor manufacturer for the
maximum allowable rotation speed.
EU version inverters (-SFE and -HFE) have integrated EMC filter.
For achieving approved input voltage rating categories:
• 460 to 480VAC – Over-voltage category 2
• 380 to 460VAC – Over-voltage category 3
To meet the Over-voltage category 3, insert an EN or IEC standard compliant
isolation transformer that is earth grounded and star connected (for Low
Voltage Directive).
At the rated voltage when using a Hitachi standard 3-phase, 4-pole motor.
The braking torque via capacitive feedback is the average deceleration torque
at the shortest deceleration (stopping from 50/60Hz as indicated). It is not
continuous regenerative braking torque. The average deceleration torque
varies with motor loss. This value decreases when operating beyond 50Hz. If
a large regenerative torque is required, the optional regenerative braking
unit and a resistor should be used.
The frequency command is the maximum frequency at 9.8V for input voltage
0 to 10VDC, or at 19.6mA for input current 4 to 20mA. If this characteristic is
not satisfactory for your application, contact your Hitachi representative.
If the inverter is operated outside the region shown in the graph to the right,
the inverter may be damaged or its service life may be shortened. Set B083
Carrier Frequency Adjustment in accordance with the expected output
current level.
Rated
current
The storage temperature refers to the short-term temperature during
transportation.
Conforms to the test method specified in JIS C0040 (1999). For the model
types excluded in the standard specifications, contact your Hitachi sales
representative.
ManualsBase.com
Derating Curve
100%
70%
Operating region
0
5.0
Curve at 40°C
kHz
12.0