monitor function D001 during each segment of a multi-speed operation.
NOTE: When using the Multi-speed Select settings CF1 to CF4, do not display
parameter F001 or change the value of F001 while the inverter is in Run Mode (motor
running). If it is necessary to check the value of F001 during Run Mode, please monitor
D001 instead of F001.
There are two ways to program the speeds into the registers A020 to A035:
1. Standard keypad programming:
2. Programming using the CF switches. Set the speed by following these steps:
More user manuals on
a. Select each parameter A020 to A035.
b. Press the
key to view the parameter value.
FUNC
c. Use the
and
keys to edit the value.
2
1
d. Use the
key to save the data to memory.
STR
a. Turn the Run command OFF (Stop Mode).
b. Turn inputs ON to select desired Multi-speed. Display the value of F001 on the
digital operator.
c. Set the desired output frequency by pressing the
d. Press the
key once to store the set frequency. When this occurs, F001
STR
indicates the output frequency of Multi-speed n.
e. Press the
key once to confirm that the indication is the same as the set
FUNC
frequency.
f. Repeat operations in 2. a) to 2. e) to set the frequency of other Multi-speeds. It  can
be set also by parameters A020 to A035 in the first procedure 1. a) to 1. d).
ManualsBase.com
and
keys.
1
2
4−13