Hitachi X200-002SFE/NFU Instruction Manuals page 253

X200 series. single-phase input 200v class. three-phase input 200v class. three-phase input 400v class.
Table of Contents

Advertisement

B−26
Func.
Code
A020
A220
A021
A022
A023
A024
A025
A026
A027
A028
A029
A030
A031
A032
A033
A034
A035
A038
A039
A041
A241
A042
A242
A043
A243
A044
A244
A045
A245
More user manuals on
Name
R/W
Multi-speed 0 setting
R/W Defines the first speed of a
Multi-speed 0 setting
R/W Defines the first speed of a
2nd motor
Multi-speed 1 setting
R/W
Multi-speed 2 setting
R/W
Multi-speed 3 setting
R/W
Multi-speed 4 setting
R/W
Multi-speed 5 setting
R/W
Multi-speed 6 setting
R/W
Multi-speed 7 setting
R/W
Multi-speed 8 setting
R/W
Multi-speed 9 setting
R/W
Multi-speed 10 setting
R/W
Multi-speed 11 setting
R/W
Multi-speed 12 setting
R/W
Multi-speed 13 setting
R/W
Multi-speed 14 setting
R/W
Multi-speed 15 setting
R/W
Jog frequency setting
R/W Defines limited speed for jog,
Jog stop mode
R/W
Torque boost select
R/W
Torque boost select,
R/W
2nd motor
Manual torque boost
R/W
value
Manual torque boost
R/W
value, 2nd motor
Manual torque boost
R/W
frequency adjustment
Manual torque boost
R/W
frequency adjustment,
2nd motor
V/f characteristic curve
R/W
selection
V/f characteristic curve
R/W
selection, 2nd motor
V/f gain setting
R/W
V/f gain setting, 2nd
R/W
motor
ManualsBase.com
List of Holding Registers
Description
multi-speed profile, range is 0.0 /
start frequency to 400 Hz
A020 = Speed 0 (1st motor)
multi-speed profile, range is 0.0 /
start frequency to 400 Hz
A220 = Speed 0 (2nd motor)
Defines 15 more speeds,
range is 0.0 / start frequency to
400 Hz.
A021= Speed 1...
A035 = Speed 15
range is 0.00 / start frequency
to 9.99 Hz
Define how end of jog stops
the motor; three options:
00...Free-run stop
01...Controlled deceleration
02...DC braking to stop
Two options:
00...Manual torque boost
01...Automatic torque boost
Can boost starting torque
between 0 and 20% above normal
V/f curve,
range is 0.0 to 20.0%
Sets the frequency of the V/f
breakpoint A in graph (top of
previous page) for torque boost,
range is 0.0 to 50.0%
Two available V/f curves;
two select codes:
00...Constant torque
01...Reduced torque
06...Reduced torque1
Sets voltage gain of the inverter,
range is 20. to 100.%
Network Data
Reg.
Range
Res.
1029h
0 / start
0.1 Hz
freq. to
4000
150Fh
0 / start
0.1 Hz
freq. to
4000
102Bh
0 / start
0.1 Hz
freq. to
102Dh
4000
102Fh
1031h
1033h
1035h
1037h
1039h
103Bh
103Dh
103Fh
1041h
1043h
1045h
1047h
1048h
0 / start
0.01 Hz
freq. to
999
1049h
0, 1, 2
104Ah
0, 1
1510h
104Bh
0 to 200
0.1 %
1511h
104Ch
0 to 500
0.1 %
1512h
104Dh
0, 1, 6
1513h
104Eh
20 to 100
1 %
1514h

Advertisement

Table of Contents
loading

Table of Contents